3

Wiring 

On/Off, 24V, 120/230V 

SY Actuator Wiring Diagram, SY1…5-24 – On/Off
                                                  SY1…12-110 (220) On/Off

Observe class 1 and class 2 wiring restrictions.

Transformer sizing = SY actuator draw X 1.25 (safety margin)

(Ex. SY2-24 requires 3.0A x 1.25 = 3.75A, 

3.75A X 24 VAC = 90VA Transformer).

Indicates an action or condition that may cause irreversible 

damage to the actuator(s) or associated equipment.

Equipment damage!

Power consumption and input impedance must be observed. 

CAUTION

Indicates a potentially hazardous situation which, if not avoided, 

may result in minor or moderate injury. It may also be used to 

alert against unsafe practices.

Warnings and Cautions appear at appropriate sections throughout 

this manual. Read these carefully.

Hazard Identification

INSTALLATION NOTES

   W546

NOTES   

SY1…5-24

          Each actuator should be powered by a single, isolated 

          control transformer.

•  Isolation relays must be used in parallel connection of multiple actuators

    using a common control signal input.

•  "H" cannot be connected to terminal #3 and #4 simultaneously.
•  

Required: 

Terminal #7 needs to be field wired to enable heater circuit.

24 VAC Transformer

Line 

Volts

Open

Close

 G     Ground

 1     Common
 3     Open
 4     Closed
 5     

Connect to #1 for fully 

               open indication

 6     

Connect to #1 for fully 

               closed indication

 7     

 G     Ground

 1     Common
 3     Open
 4     Closed
 5     

Connect to #1 for fully 

               open indication

 6     

Connect to #1 for fully 

               closed indication

 7     

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY2…5-24

120 and 230 VAC

G

Open

Close

G

N L1

H L2

HTR

 A
 B
 C
 D
 E
 F

LS3

A-C 

(Open Indication)

LS4

D-F 

(Closed Indication)

Contact Rating: 5A 250 VAC Max.

SY2…12-110 (220)

NOTES   

SY1…12-110 (220)

•  

Caution:

 Power Supply Voltage

•  Isolation relays must be used in parallel connection of multiple actuators

    using a common control signal input.

•  "H" (L2) cannot be connected to terminal #3 and #4 simultaneously.
•  

Required: 

Terminal #7 needs to be field wired to enable heater circuit.

SY1-24

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.

                          3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY1-110 (220)

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.

                          3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY1 Contact Arrangements

33

33

W546

Actuators:   SY4...12-110       SY4...12-220

SY4...5-24 

SY4...12-110 (220) 

SY4...5-24 

SY4...12-110 (220)

71

90

6-

00

00

1  S

ub

je

ct t

o c

ha

ng

e. © B

el

im

o A

irc

on

tro

ls (

US

A)

, I

nc

.

Отзывы: