Wiring Diagrams
203
J20741 - Subject to change. © Belimo Aircontrols (USA), Inc.
LM
LMCB24-3 (-T)
On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V
LMCB24-3 - Typical Specification:
Floating point, on/off control damper actuators shall be elec-
tronic direct-coupled type, which require no crankarm and link-
age and be capable of direct mounting to a shaft from 1/4” to
5/8”. Shafts up to 3/4” diameter can be accommodate with an
accessory clamp. Actuators shall have Brushless DC motor
technology and be protected from overload at all angles of rota-
tion. Actuators shall have reversing switch and manual override
on the cover. If required, actuator will be provided with screw
terminal strip for electrical connections (LMCB24-3-T). If
required, actuators shall be provided with one adjustable SPDT
auxiliary switch. Actuators with auxiliary switches must be con-
structed to meet the requirements for double insulation so an
electrical ground is not required to meet agency listings. Run
time shall be constant and independent of torque. Actuators
shall be cULus listed, have a 5-year warranty, and be manu-
factured under ISO 9001 International Quality Control
Standards. Actuators shall be as manufactured by Belimo.
Accessories
K-LM20
3/4” [20 mm] Shaft Clamp
AV6-20
Shaft Extension
ZG-LMSA
Shaft Adaptor for 1/2” Diameter Shafts
ZG-LMSA-1
Shaft Adaptor for 3/8” Diameter Shafts
ZS-T
Terminal Cover for NEMA 2
ZS-100
Weather Shield - Steel
ZS-150
Weather Shield - Polycarbonate
Tool-06
8 mm & 10 mm Wrench
S1A, S2A
Auxiliary Switch (es)
P370
Shaft Mount Auxiliary Switch
P…A
Feedback Potentiometers
Note: When using LMCB24-3… actuators, only use acces-
sories listed on this page.
1
2
4
24 VAC Transformer
a open
a closed
The indication of direction
is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
a
Line
Volts
–
1
0
W266
1
2
4
24 VAC Transformer
The indication of direction
is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
Line
Volts
–
1
0
W267
On/Off
4
1
2
Provide overload protection and disconnect as required.
Actuators may also be powered by 24 VDC.
Meets cULus requirements without the need of an
electrical ground connection.
Notes:
Floating Point or On/Off control
®