Display and touch keypad

Operation instructions

On/Off

Mode

Fan speed

Temperature adjustment

EXT-CFU-230-D.. Touch Keypad Thermostat

It shows following status:

·

working status: cool     , heating     or ventilation

·

fan speed: low     ,Mid         ,High             ,or Auto

·

FCU valve status

·

Room temperature

·

Temperature setpoint 

·

Time, week display

On/Off

Press “    ” to turn on, press “     ”again to turn off thermostat and its output.

Setting Temperature

Press “    ” to reduce temperature, press 

“▲”

 to raise temperature (0.5°C per step).

Mode Selection

Press “M” to change system working in cooling “     ”, heating “     ” or ventilation “     ” mode.

Fan Speed Selection 

Press “     ” to select              (Hi),           (Med),      (Low), AUTO(Auto).

In “Auto” mode, the fan-speed changes automatically. When the differential temperature 

between room temperature and setpoint exceeds 1°C, 2°C and 3°C, thermostat operates at Auto

LOW-speed, Auto MED-speed and Auto HI-speed respecctively.

Control Motorised Valve Under 

If the differential temperature between room temperature and setpoint exceeds 1°C, FCU valve 

will be opened; if room temperature and setpoint are equal, the thermostat will close the FCU  

valve with the fan kept running.

Keypad Lock Function

Keypad Lock:
Keypad Unlock: 

Press “     ” for 5 seconds to unlock.

Low Temperature Protection Function

Turn on: 

 When the room temperature is lower than 5°C, the thermostat will automatically 

turn on the fan and valve (with “     ” showing). When the room temperature is increased to 7°C, 

the thermostat will automatically stop output. 

Low Temperature Protection Setting

Turn off: 

Press “M” and hold for 3 seconds, it will display “OF” or “ON”. Press 

“▲”

 or 

“▼”

 to adjust

the parameter. “OF” indicates low temperature protection is turned off, “ON” indicates low

temperature protection function is turned on (Factory default setting is “OF”).

In case that the user wants the displayed temperature on the thermostat higher or lower than 

the real temperature(±5°C), the following operations could be taken:

Turn off: 

Press 

“▲”

 and  

“▼”

 at the same time for 3 seconds, it will display “XX°C”, press 

“▲”

 or  

“▼”

 to adjust the temperature value, it will be automatically confirmed after 6 seconds. 

Alarm

If the sensor has failure, the thermostat will close the fan and valve, displaying “E1” or “E2”.

E1: Sensor in short circuit alarm

E2: Sensor in open circuit alarm

It displays “HI” when the temperature is higher than 55°C , displaying “LO” when the tempera-

ture is lower than 0°C.

If there is no key operation for 30 seconds, the  keypad will be locked automatically. 

Offset adjustment of temperature display

In cooling, when the room temperature is higher than set-point, the cooling Valve will be opened. 

temperature is lower than set-point, the heating valve will be opened. Otherwise it will be closed. 

Cooling valve is always closed.

Otherwise it will be closed. Heating valve is always closed. In heating, When the room 