background image

Technical data sheet

EP..F+MP

Characterised control valve with 

sensor-operated flow control, 2-way, 

Flange, PN 16 (EPIV)

• Nominal voltage AC/DC 24 V

• Control modulating, communicative

• For closed cold and warm water

systems

• For modulating control of air-

handling and heating systems on the

water side

• Communication via Belimo MP-Bus

or conventional control

• Conversion of active sensor signals

and switching contacts

Type overview

Type

DN

[ ]

DN

[“]

V’nom

[ l/s]

V’nom

[ l/min]

kvs theor.

[ m³/h]

PN

[ ]

n(gl)

[ ]

MP

65

2 1/2

8

480

50

16

3.2

MP

80

3

11

660

74

16

3.2

MP

100

4

20

1200

126

16

3.2

MP

125

5

31

1860

195

16

3.2

MP

150

6

45

2700

254

16

3.2

kvs theor.: Theoretical kvs value for pressure drop calculation

Technical data

Electrical data   Nominal voltage

AC/DC 24 V

Nominal voltage frequency

50/60 Hz

Nominal voltage range

AC 19.2...28.8 V / DC 21.6...28.8 V

Power consumption in operation

9.5 W

Power consumption in rest position

6.5 W

Power consumption for wire sizing

13 VA

Connection supply / control

Cable 1 m, 4 x 0.75 mm²

Parallel operation

Yes (note the performance data)

Functional data   Torque Motor

20 Nm (DN 65...80)

40 Nm (DN 100...150)

Operating range Y

DC 2...10 V

Input Impedance

100 kΩ

Operating range Y variable

Start point DC 0.5...24 V

End point DC 8.5...32 V

Options positioning signal

Modulating (DC 0...32 V)

Position feedback U

DC 2...10 V

Position feedback U note

Max. 1 mA

Position feedback U variable

Start point DC 0.5...8 V

End point DC 2...10 V

Sound power level Motor

45 dB(A)

Adjustable flow rate V’max

30...100% of Vnom

Control accuracy

±

5

% (of 25...100% Vnom) @ 20°C / Glycol 0% 

vol.

Media

Cold and warm water, water with glycol up to 

max. 

6

0% vol.

Medium temperature

-10...120°C

Close-off pressure ∆ps

690 kPa

Differential pressure  ∆pmax

340 kPa

Flow characteristic

equal percentage (VDI/VDE 2178), optimised in 

the opening range (switchable to linear)

Leakage rate

air-bubble tight, leakage rate A (EN 12266-1)

Pipe connectors

Flange PN 16 according to EN 1092-2

Installation position

upright to horizontal (in relation to the stem)

Servicing

maintenance-free

Manual override

with push-button, can be locked

www.belimo.com

EP..F+MP • en-ap • 2019-06-03 • subject to changes

1

Содержание EP065F+MP

Страница 1: ...13 VA Connection supply control Cable 1 m 4 x 0 75 mm Parallel operation Yes note the performance data Functional data Torque Motor 20 Nm DN 65 80 40 Nm DN 100 150 Operating range Y DC 2 10 V Input I...

Страница 2: ...ording to the data sheet Only authorised specialists may carry out installation All applicable legal or institutional installation regulations must be complied during installation The connection betwe...

Страница 3: ...water volumetric flow Curve 1 With the classical type of temperature control an attempt is made to maintain the control signal Y proportional to the power Q Curve 2 This is achieved by means of an equ...

Страница 4: ...l parameters in connection with the precise flow rate sensor ensure a stable quality of control They are however not suitable for rapid control processes i e for domestic water control U5 displays the...

Страница 5: ...contact The MP actuator serves as an analogue digital converter for the transmission of the sensor signal via MP Bus to the higher level system Configurable actuators The factory settings cover the m...

Страница 6: ...actuators VAV controller and HVAC performance devices ZTH AP Belimo PC Tool Software for adjustments and diagnostics for MF MP MOD LON KNX actuators incl fire protection CD with Software and instructi...

Страница 7: ...2 V Resolution 30 mV 1 2 3 5 MP T U Y A p A more actuators and sensors max 8 Switching current 16 mA 24 V Start point of the operating range must be parameterised on the MP actuator as 0 5 V Functions...

Страница 8: ...under normal circumstances even filling water with a lower conductivity will experience an elevation of its conductivity to above the minimum required value during filling and that the system can thu...

Страница 9: ...ial pressure pressure drop The minimum required differential pressure pressure drop through the valve for achieving the desired volumetric flow max can be calculated with the aid of the theoretical kv...

Страница 10: ...ed as necessary Type DN L mm H mm D mm d mm K mm X mm Y mm Weight EP065F MP 65 379 205 185 4 x 19 145 220 150 26 kg EP080F MP 80 430 205 200 8 x 19 160 220 160 35 kg EP100F MP 100 474 221 229 8 x 19 1...

Отзывы: