ZIP Economizer
Setup and Configuration
Quick Setup
MMI Keypad
Moves up through the
menu on the same level.
Will increase values by
one increment at a time.
When setting values
holding key down will
fast scroll
Moves down through the
menu on the same level.
Will decrease values by
one increment at a time.
When setting values
holding key down will fast
scroll.
Enter sub menu level.
Start editing a setting.
Store an entered
value.
esc
Escape sub menu to
next higher level.
Cancel current actions.
i
Show additional
information on the
current menu Item
when “i” appears in
lower right of display.
Functions
1. “Monitor Live Conditions” is used to display settings and live values.
2. “Settings” is used to parameterize the ZIP Economizer. (Note: Devices 1 is
for CC1, CC2, EF, IF; Devices 2 is for OAH, RAH)
3. “Present Devices” is used to verify that the ZIP Economizer's Auto Detected
connections are terminated properly. If connected device is not shown,
verify wiring. If wiring has continuity and device is verifi ed operational
re-enter “Settings” and enable missing device by changing from “Auto” to
“Available” or “Installed”.
4. “Alarms” is used to view current and historical alarms and delete
inadvertently caused alarms.
5. “Service and Commissioning” submenu is used to operate the RTU in
“Manual Mode” or to perform “Acceptance Test”. “Settings” must to be
completed to access.
6. “Status” is a display of the current operating mode. It can be accessed
by pressing ”esc”. The action of pressing any key will drop the user down
from Status to the next level, so repeatedly pressing “esc” will toggle the
display between Status and Monitor Live Conditions.
(Note: If status
“Setup incomplete” is displayed the RTU cooling operation will be
disabled and additional parameters must be set to achieve “Setup
complete”.)
Installation
1. Shut off power to RTU before beginning installation.
2. Note orientation, opening rotation, and spring return rotation of damper
assembly. Mount Actuator to Outside Air and Return Damper assembly.
To ensure tight outside air shutoff; while tightening actuator clamp push
damper closed.
3. Terminate required Inputs and Outputs(I/O): For the ZIP Economizer to
function correctly, the following I/O, at a minimum, are required to be
terminated, wired, and functioning (R, C, Y1, Y2, G, CC1, OAT, SAT, ACT1,
ACT2, ACT3, ACT5). See wiring diagrams.
4. Sensor confi guation: The ZIP Economizer automatically detects sensors
attached and automatically confi gures for single dry bulb, single enthalpy,
differential dry bulb and differential enthalpy.
Settings
“Settings” is the menu displayed when the ZIP Economizer is fi rst powered.
Press “OK” to parameterize required settings. Reference above Keypad Key
defi nition instructions and navigate as needed.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualifi ed licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.