Functions

CR24-..

18

www.belimo.com

Pr

oduct information S4-CR24-.. • en • v2.3 • 08.2022 • Subject t

o changes

Y [V]

t

R

 [°C]

W

A

10

2

0

V

max

.

V

min

.

Y [V]

t

R

 [°C]

W

A

10

8.4

2
0

ao1

ao2

ao3

ao1

V

max

.

V

min

.

If a local detector (e.g. a window switch) acts on the digital input di1 and 

closes the corresponding contact, the room is adjusted to the building 

protection settings in energy saving mode, in other words the heating 

setpoint is significantly reduced (15°C) or the cooling setpoint signifi

-

cantly increased (40°C), though not sufficiently to cause damage to sen

-

sitive objects (plants, paintings etc.).

Typical applications

–  A window switch at di1 stops all energy consumption from the mo

-

ment the window is opened until the lower or upper building protec

-

tion limit is reached.

–  Higher-level override command, e.g. building management system.

Notes

–  The minimum VAV output is set to 0 V instead of 2 V while energy hold 

off is active (forced closing in 2...10 V) 

–  The mode switch (operator level 1) is deactivated while energy hold 

off is active (input di1 takes priority).

–  If an external temperature sensor is used, the frost limit is monitored 

by the internal sensor while energy hold off is active.

–  Due to the automatic sensor detection the change into energy hold off 

takes about 40 seconds.

If a local detector (e.g. a motion detector) acts on the digital input di2 

and closes the corresponding contact, the room is adjusted to the stand-

by settings, in other words the heating setpoint is reduced by 2 K or the 

cooling setpoint is increased by 3 K.

Typical applications

–  A motion detector, a light switch or another detector at di2 reduces 

the energy consumption of unoccupied rooms.

–  Higher-level override command, e.g. building management system.

Y [V]

t

R

 [°C]

W

A

10

2

0

V

max

.

V

min

.

1 2

4

~

+

di2

AC 24 V

CR24-B..

Stand-by

Stand-by

Energy hold off

Digital input di1

all CR24-..

Stand-by

Digital input di2

all CR24-..

If the selected application requires an increased air volume for heating, 

e.g. for:

–  Providing or assisting heating with air.

–  Improving the air quality during heating.

VAV function: air volume in heating mode (Reheater)

CR24-B2 und CR24-B3 only

CR24-B2 configuration

The VAV function is configured using DIP switch 2.

1

2

CR24-B3 configuration

The VAV function is configured using DIP switch 2.

6

1

2

4

3

5

V'

max

 heating

closed

1 2

3

~

+

ai/di1

AC 24 V

NTC

CR24-B..

Energy hold off

Energy hold off

Key

Output signal

t

R

 

Room temperature

W

A

 

Current setpoint

Key

Output signal

t

R

 

Room temperature

W

A

 

Current setpoint

Key

Output signal

t

R

 

Room temperature

W

A

 

Current setpoint

Содержание CR24 Series

Страница 1: ...Single room controllers CR24 B2E CR24 A2E Single room controllers CR24 B3 CR24 A3 Single room controllers 5 7 9 13 Operation 15 Functions Setpoint calculation Energy hold off Stand by VAV Function Ele...

Страница 2: ...oduct information S4 CR24 en v2 3 08 2022 Subject to changes VAV applications Single room controllers Water applications Air applications CR24 B1 CR24 B2E CR24 B3 CR24 B2 Compact Universal Rotary actu...

Страница 3: ...st effective system solutions for individually controlling the room climate and reducing energy consumption The controllers can be used in both pure VAV and combined systems with 2 and 4 pipe water ap...

Страница 4: ...d Volume increase in heating mode selectable Internal function test including nominal voltage test Commissioning mode with output and sequence simulation VAV controller diagnosis via integrated PC Too...

Страница 5: ...otection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without condensation Trans...

Страница 6: ...y unoccu pied Frost The frost protection function is activated if the actual room temperature falls below 10 C Change over Change over heating or heating cooling External temperature sensor An externa...

Страница 7: ...f approx 150 s Norms und standards Protection class III Safety extra low voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE con...

Страница 8: ...cted to the analog input ai1 for instance in order to measure the average room temperature in the exhaust air duct External setpoint shift An external DC 0 10 V signal at the analog input ai2 can be u...

Страница 9: ...oltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH without...

Страница 10: ...ion can optionally be increased Output mode The do3 output mode can be set accordingly to the application to stage for one stage electrical reheater or on off radiator valve binary for two stage elect...

Страница 11: ...former Parallel connection of other actuators possible Note the performance data Inputs Outputs 3 ai1 Supply air temperature limiter 6 ao1 System output for Belimo VAV controller di1 Energy hold off 9...

Страница 12: ...12 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Страница 13: ...w voltage Degree of protection IP 30 to EN 60529 Mode of operation Type 1 to EN 60730 1 Software class A to EN 60730 1 EMC CE conformity to 89 336 EEC Ambient conditions Operation 0 50 C 20 90 RH with...

Страница 14: ...shift An external DC 0 10 V signal at the analog input ai2 can be used to shift the basic setpoint 0 10 K for instance for the summer winter compensation These functions are described in detail on pag...

Страница 15: ...also during operation Internal function test A comprehensive internal function test including a nominal voltage test AC 24 V can be started for the controller with the mode switch The three LEDs statu...

Страница 16: ...16 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Страница 17: ...mfort Basic setpoint WH 3 K Setpoint adjustment Setpoint shift 0 10 V Comfort heating setpoint WA 1 K Dead band Stand by Comfort heating setpoint WA 2 K Stand by offset heating Comfort heating setpoin...

Страница 18: ...to the automatic sensor detection the change into energy hold off takes about 40 seconds If a local detector e g a motion detector acts on the digital input di2 and closes the corresponding contact t...

Страница 19: ...60 70 80 C 30 40 50 60 70 80 An external NTC temperature sensor can be connected to the analog input ai1 Sensor type NTC 5k 5 k Function The temperature of the supply air is limited by shedding indi...

Страница 20: ...rooms hotel rooms etc e g time switch controlled Assisting smoke extraction Controlling air quality 2 point signal Notes The VAV output ao1 is set to a fixed value of V max 10 V The heating output ao3...

Страница 21: ...ting cooling output ao2 of the CR24 B3 controller Typical applications Change over heating or heating cooling Note For chilled ceiling applications refer to page 23 The CR24 B1 controller is suitable...

Страница 22: ...litate room preconditioning Boost V max Digital input di3 CR24 B3 only Configuration This boost function is configured using DIP switches 4 boost on and 5 boost V max 2 3 4 5 6 1 Configuration CR24 B3...

Страница 23: ...ng can be combined with the change over function Typical applications Switchable heated chilled ceiling systems that also require dew point limiting Chilled ceiling with dew point limiting Digital inp...

Страница 24: ...the local safety interlock STh from responding unless absolutely necessa ry and relieves the load on devices and installations When the system is started up after a power on or EHO off or when EHO ac...

Страница 25: ...sing cover 2 Pull out slightly the wall of the housing to release the pcb 3 Remove the printed circuit board Rotary knob for setpoint adjustment If the rotary knob has been removed proceed as follows...

Страница 26: ...y of the environment No of CR24 Cable cross section Cable length 10 0 75 mm2 max 250 m 20 0 75 mm2 max 200 m 20 1 00 mm2 max 250 m 25 0 75 mm2 max 170 m 25 1 00 mm2 max 220 m 25 1 50 mm2 max 250 m 30...

Страница 27: ...with the mode switch on the operator panel With CR24 A controllers the housing cover must be removed first To activate test mode 1 Set the mode switch to MAX The red LED MAX status indication lights...

Страница 28: ...ated without a flow Simulations can be carried out on the CR24 at any time even if the ventilation system is not operating The two triac outputs are activated for a maximum of 15 seconds in simulation...

Страница 29: ...www belimo com 29 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Страница 30: ...30 www belimo com Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Страница 31: ...www belimo com 31 Product information S4 CR24 en v2 3 08 2022 Subject to changes...

Страница 32: ...m Agentina Australia Bahrain Belgium Bosnia Herzegovina Brazil Bulgaria Canada Chile Croatia Cyprus Czech Republic Denmark Egypt Estonia Finland France Great Britain Germany Greece Hong Kong Hungary I...

Отзывы: