2

WIRING DIAGRAMS

CQ..24V, CQB24-3, CQB24-SR (-L) (-R)

24 VAC Transformer

Blk         Common

Wht        + 

Red        

Line 
Volts

A

2

3

18

Functions

A

100%

0%

Notes:

On/Off, CQB24-3

Floating Point, CQB24-3

Line 
Volts

Control Signal

VDC/mA

Blk           Common

Red          + Hot

Wht          Y

Input, 2 to 10V

500

2

3

18

5

7

2 VDC

Open

10 VDC

Close

24 VAC Transformer

Line 
Volts

Control Signal

VDC/mA

Blk           Common

Red          + Hot

Wht          Y

Input, 2 to 10V

500

2

3

18

5

7

2 VDC

Close

10 VDC

Open

Proportional, CQB24-SR-L

Proportional, CQB24-SR-R

CQ..110-240V, CQBUP-3

110 to 230 VAC

Blu         Common

Wht

        + 

Brn        + 

Line 
Volts

A

2

18

A

Functions

100%

0%

Blu        Common

Brn        +

Wht        +

Line 
Volts

A

B

2

18

Functions

100%

0%

A

B

On/Off, CQBUP-3

Floating Point, CQBUP-3

Meets cULus requirements without the need of an 
electrical ground connection

2

Actuators may be connected in parallel. Power 
consumption and input impedance must be 
observed.

3

Actuators may also be powered by 24 VDC.

5

Only connect common to neg. (-) leg of control 
circuits.

7

A 500 Ω (ZG-R01) converts the 4 to 20 mA control 
signal to 2 to 10 VDC.

18

Actuators with plenum rated cable do not have 
numbers on wires; use color codes instead.

BL

K

Bl

ac

k

Ne

g

ro

No

ir

Pr

eto

RED

Re

d

Ro

jo

R

ouge

Ve

rm

el

h

o

WHT

Wh

ite

Bl

an

co

Bl

an

c

Br

an

co

kg

>122°F

PIQCV

!

kg

QCV

Functions

100%

0%

A

B

1        Common

2

        

+

3        +

Line 
Volts

A

B

2

3

18

Отзывы: