Control and monitoring of
motorized fire and smoke dam-
pers 

in combination with the

Communication and Power
Supply Unit BKN230-24

Mode of operation

The BKS24-1B unit receives status infor-
mation about the fire and smoke damper
and issues control commands to it via
the Communication and Power Supply
Unit BKN230-24.

LEDs

on the front of the unit signal the

operating status of the damper and the
presence of faults anywhere in the
system.

Floating auxiliary contacts

allow the

unit to be linked into higher level systems
(such as damper end position indicators,
fault alarms, fan enabling, etc.).

Function testing

of the fire and smoke

damper systems by pressing the 
“RESET/TEST” pushbutton.

Accessory

ZSO-11 plug socket suitable for 35 mm
DIN rail mounting.

Detailed functional sequences

see

over.

Typical wiring diagram

see over.

Communication and Control Unit BKS24-1B

Dimensions

T

~

AC 24 V

Fault

SAFE damper
position

NORMAL
damper position

Connect via
safety isolating
transformer

!

2

10

1

5

Reset

Test

AC
24 V

BKS24-1B

6

4

3

7

8

Control
ON / OFF

Connections
interchangeable

optional external

pushbutton

9

11

2-wire conductor
to BKN230-24

a

b

Open

Close

Alarm

Reset
Test

Note: Relay contacts are shown without power applied.

Wiring digram

Power consumption

2.5 W 

Auxiliary switches

6 A (2 A), AC 24 V

Protection class

(safety low voltage)

Connection

Submagnal connector 11 pole, suitable for ZSO-11 socket

(ZSO-11 plug socket not included, order separately!)

For wire sizing

3 VA

Nominal voltage

AC 24 V   50/60Hz

Nominal voltage range

AC 19.2...28.8 V

Technical data

BKS24-1B

Maintenance

maintenance free

Degree of protection

IP 30

Ambient temperature range

0...+ 50 °C

EMC

CE according to 89/336/EEC

Weight

150 g

Damper in the 

safe position

Causes / Sequence

No AC 24 V

 power supply

Signalling and diagnosis

LEDs

Alarm

Open Close

Contacts

Description

OFF

OFF

OFF

ON

ON

ON

Test run ca. 35 s

, triggered by: AC 24 V energising or by pressing

“Reset / Test”

flash

Status

OFF

OFF

New fault,

 possible causes: • Short-circuit or open-circuit in 2-wire conductor

or damper fault (BKN...) • No AC 230 V • Defective thermal trip • Smoke
detector triggered • Running time exceeded  • Damper jammed

6

3

6

3

6

3

OFF

OFF

ON

Stored fault

 • Signal given that there has been a fault in the system and it

should be checked

6

3

flash

6

4

OFF

OFF

Damper (actuator) 

moving to

 the safe position

OFF

OFF

6

4

ON

flash

8

7

OFF

OFF

Damper (actuator) 

moving to

 the operating position

OFF

OFF

8

7

ON

Damper in the 

operating position

p0036707

w0622810

35

20

70

ZSO-11

BKS24-1B

65

BKS24-1B

ZSO-11: Width = 38 mm

d0050810

B

C

III