Functional profile according to LONMARK®
The LON-capable actuator is certified by LONMARK®. Die following actuator functions are made available via the LONWORKS®
network as standardised network variables in accordance with LONMARK®: the Node Object #0, the Damper Actuator Object
#8110, the Open Loop Sensor Object #1 and the Thermostat Object #8060.
Node Object #0
nviRequest
SNVT_obj_request
nvoStatus
SNVT_obj_status
nvoFileDirectory
SNVT_address
Configuration Properties
SCPTdevMajVer (165)
SCPTdevMinVer (166)
SCPTobjMajVer (167)
SCPTobjMinVer (168)
Node Object #0
The node object contains the object status and object request
functions.
nviRequest: SNVT_obj_request
Input variable for requesting the status of a particular object in the
node.
nvoStatus: SNVT_obj_status
Output variable that outputs the current status of a particular object
in the node.
nvoFileDirectory: SNVT_address
Output variable that shows information in the address range of the
Neuron chip.
nviRelStpt
SNVT_lev_percent
nviActuatState
SNVT_switch
nvoActualValue
SNVT_lev_percent
nvoAbsAngle
SNVT_angle_deg
nvoAbsAirFlow
SNVT_flow
Configuration Properties
nviManOvrd
SNVT_hvac_overid
Damper Actuator Object #8110
SCPTobjMajVer (167)
SCPTobjMinVer (168)
SCPTminSendTime (52)
SCPTmaxSendTime (49)
SCPTmaxRcvTime (48)
SCPTminDeltaAngl (43)
SCPTminDeltaFlow (47)
SCPTserialNumber (179)
SCPTactuatorType (41)
SCPToemType (61)
SCPTlocation (17)
SCPTnomAngle (58)
SCPTnomAirFlow (57)
SCPTminSetpoint (53)
SCPTmaxSetpoint (50)
SCPTdriveTime (45)
SCPTdirection (44)
Damper Actuator Object #8110
The actuator object is used to display the functions of the actuator
on the page of the LONWORKS® network.
nviRelStpt: SNVT_lev_percent
The nominal position is assigned to the actuator via this input
variable. This variable is normally linked to the output variable of an
HVAC controller.
nviActuateState: SNVT_switch
A preset position is assigned to the actuator via this input variable.
Note on priority: The variable which was most recently active, either
nviActuatorState or nviRelStpt, has priority.
nviManOvrd: SNVT_hvac_overid
This input variable can be used to manually override the actuator
into a particular position.
nvoActualValue: SNVT_lev_percent
This output variable shows the current actual position of the actuator
and can be used for control circuit feedback or for displaying
positions.
nvoAbsAngle: SNVT_angle_deg
This output variable shows the current angle of rotation / stroke of
the actuator and can be used to display the position or for service
purposes.
nvoAbsAirFlow: SNVT_flow
This output variable is inactive with this actuator and shows a
constant value of 65535 (this variable is only active in conjunction
with LON-capable VAV controllers).
Open Loop Sensor Object #1
nvoSensorValue
SNVT_xxx
Configuration Properties
SCPTobjMajVer (167)
SCPTobjMinVer (168)
SCPTminSendTime (52)
SCPTmaxSendTime (49)
SCPTsndDelta (27)
SCPTmaxNVLength (255)
SCPTnvType (254)
UCPTadFunction (1)
UCPTadTransformation (2)
SCPTtrnsTblX (28)
SCPTtrnsTblY (29)
SCPTinvrtOut (16)
Open Loop Sensor Object #1
One sensor can be connected to the actuator.
A passive resistance sensor (e.g. Ni1000), an active sensor (output
0 ... 32 V) or a switch (On/Off) can be connected. In the case of
the open loop sensor object, the measured sensor values are
transferred to the LONWORKS® network.
nvoSensorValue: SNVT_xxx
This output variable shows the current sensor value. Depending on
the connected sensor, the output variable can be configured via the
sensor plug-in and specifically adapted to the system.
The SNVT_.. can be configured as:
SNVT_temp_p
SNVT_lev_percent
SNVT_lux
SNVT_temp
SNVT_abs_humid
SNVT_press_p
SNVT_switch
SNVT_enthalpy
SNVT_smo_obscur
SNVT_flow
SNVT_ppm
SNVT_power
SNVT_flow_p
SNVT_rpm
SNVT_elec_kwh