STANDARD RECOMMENDED PROCEDURE                                     PX106485-EN  REV A                                  Page 2 of 8

Pigtail: 63in approx.

Routing fiber splice cassette

 

The following instructions describe fiber routing and splicing inside the splice cassette. Please take note that the splice cassette is  

 

adapted for splicing and managing 900μm (tight buffer) and 250μm optical fiber.

 

1

  Cable preparation: Leave 53in approx. of sub-unit and another 34in approx. of 900μm. 

 

 

Pigtail preparation: Leave 63in approx. of 900μm fiber.

Thight buffer: 34in approx.

Sub-units: 53in approx.

Cable Jacket

 

2

  Open the splice cassette. 

 

  Remove the cover.

Содержание FX ECX Cassette OM4 12P Splice

Страница 1: ...gu a de instalaci n en espa ol FR Veuillez visiter notre site web au www belden com pour obtenir le guide d installation en fran ais STANDARD RECOMMENDED PROCEDURE PX106485 EN REV A Page 1 of 8 Carto...

Страница 2: ...he splice cassette Please take note that the splice cassette is adapted for splicing and managing 900 m tight buffer and 250 m optical fiber 1 Cable preparation Leave 53in approx of sub unit and anoth...

Страница 3: ...ARD RECOMMENDED PROCEDURE PX106485 EN REV A Page 3 of 8 3 Secure the end of the sub unit with the provided cable tie 4 Loop the fiber twice 2 as shown Make sure fiber is well positioned under routing...

Страница 4: ...DARD RECOMMENDED PROCEDURE PX106485 EN REV A Page 4 of 8 5 Reinstall and close the cover 6 Flip the cassette Route the sub unit cable under the routing tabs as shown Secure it with the provided cable...

Страница 5: ...URE PX106485 EN REV A Page 5 of 8 7 Flip the cassette Open the cover Mate connectors to adapters 8 Route the pigtails as shown by looping twice 2 in the cover In order to prepare for splicing unloop 9...

Страница 6: ...STANDARD RECOMMENDED PROCEDURE PX106485 EN REV A Page 6 of 8 9 Splice the 900 m fiber tight buffer to the pigtails...

Страница 7: ...A Page 7 of 8 10 Route the pigtails by doing another loop in the cover Route the 900 m fiber tight buffer by doing another loop in the housing as shown 11 Insert the spliced fiber into the universal s...

Страница 8: ...STANDARD RECOMMENDED PROCEDURE PX106485 EN REV A Page 8 of 8 12 Manage the rest of the fiber as shown Store it under the routing tabs...

Отзывы: