background image

TCP3500-1024G

 

3

 

 

 

 

Asia-Pacific 

+86 755 298 85888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2020 Bel Power Solutions & Protection

 

BCM.00495_D 

 

CONNECTORS POSITION 

 

 

Fig. 1   Rear View - Connectors Position

 

INPUT POWER CONNECTOR: PINOUT 

Connector type: 

   Weidmüller 1081850000 

Mating part: 

   Weidmüller 1173520000 

SIGNAL NAME 

PIN # 

TYPE 

RECOMMENDED WIRES 

V MAX 

I MAX 

Earth 

 

Earth / Chassis  

Min. 2.5 mm

2

 

 

AC Line 1 

L1 

Input Power AC Fused 

Min. 2.5 mm

2

 

528 Vrms (line to line) 

16 Arms (per line) 

AC Line 2 

L2 

Input Power AC Fused 

Min. 2.5 mm

2

 

AC Line 3 

L3 

Input Power AC Fused 

Min. 2.5 mm

2

 

POWER OUTPUTS CONNECTOR 

 +/- BUS-BARS 

Connector type: 

   Bus-bar see Fig.1 

Mating part: 

   Ring terminal for M4 screws, with appropriate cross section for wire. 

SIGNAL NAME 

PIN # 

TYPE 

SIGNAL REFERENCE 

LOW LEVEL 

HIGH LEVEL 

V MAX 

I MAX 

Vout+ 

Output Power DC 

Vout- 

32 VDC 

125 ADC 

Vout- 

Output Power DC 

Note:

 Maximal mounting torque for the BUS-BARS is 2.0 Nm (please see the Fig. 2) 

Содержание TCP3500-1024G

Страница 1: ...MSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühlen des Gerätes bevor Sie es berühren Lassen Sie keine Flüssigkeiten oder Fremdkörper in die Geräte eindringen Um Überschläge zu vermeiden schließen Sie das Gerät nicht an oder trennen Sie es nicht ohne vorher die E...

Страница 2: ... Therefore the sellers and users are required to take caution in this regard 2 The AC Leakage Current exceeds 3 5mA at maximal input voltage and frequency 3 x 528Vac 60Hz Typical values are 1 8mA at input 3 x 200 208Vac L L 50 60Hz 3 0mA at 3 x 400Vac L L 50Hz and 4 1mA at 3 x 528Vac L L 60Hz 3 Switch off the input AC power before doing any intervention or manipulation with the unit Do not touch o...

Страница 3: ... Earth Earth Chassis Min 2 5 mm2 AC Line 1 L1 Input Power AC Fused Min 2 5 mm2 528 Vrms line to line 16 Arms per line AC Line 2 L2 Input Power AC Fused Min 2 5 mm2 AC Line 3 L3 Input Power AC Fused Min 2 5 mm2 POWER OUTPUTS CONNECTOR BUS BARS Connector type Bus bar see Fig 1 Mating part Ring terminal for M4 screws with appropriate cross section for wire SIGNAL NAME PIN TYPE SIGNAL REFERENCE LOW LE...

Страница 4: ...ail Warning open collector external pull up needed to max 7 V SRTN 0 4 VDC Pull up 7 VDC 20 mA OUT OK 5 Output Voltage Fault open collector external pull up needed to max 7 V SRTN 0 4 VDC Pull up 7 VDC 20 mA INHIBIT 6 Output Inhibit Open circuit or High to SRTN shuts OFF Vout SRTN 0 4 VDC 2 5 VDC 3 6 VDC 0 2 mA ENABLE 7 Power Supply Enable pin for unit enable short this pin to SRTN SRTN 0 4 VDC 2 ...

Страница 5: ...Supply Enable pin for unit enable short this pin to SRTN SRTN 0 4 VDC 2 5 VDC 3 6 VDC 0 2 mA SRTN1 8 Internal Ground Signal Return RS485 1B 9 RS485 Half Duplex Differential pair 1 RS485 1B 60 mA 60 Ω 50 pF 7 to 12 VDC 8 mA RS485 2B 10 RS485 Half Duplex Differential pair 2 RS485 2B 60 mA 60 Ω 50 pF 7 to 12 VDC 8 mA Not Connected 11 OT FAIL 12 Over Temperature PSU Fail open collector external pull u...

Страница 6: ...r supply should be 5 C at worst case total power dissipation of each PSU max 300W Recommended is to use heat transfer paste with thermal conductivity 2 5 W m K between unit and cold plate surface roughness Ra 3 2 of the aluminum plate is acceptable Recommended tightening torque of M4 screws for assembling unit to aluminum cold plate is 3 5 4 Nm 1 Note 1 Recommendation is for thread cut in aluminum...

Отзывы: