background image

3

 

INSTALLATION INSTRUCTION 

 

 

Manufacturer 

Bel Fuse Inc. 

206 Van Vorst St. 

Jersey City  

NJ 07302, USA 

Asia-Pacific 

+86 755 2988 5888

 

Europe, Middle East 

+353 61 49 8941

 

North America 

+1 866 513 2839

 

© 2021 Bel Power Solutions & Protection

 

BCM.20051_A

 

 

FIG. 1 - CONNECTIONS 

FIG. 2 - DIMENSIONS 

FIG. 3 - DISTANCES 

 

* Pin 8 and the grounding screw (at the bottom) are 
interconnected. Either Pin 8 or the grounding screw 
need to be connected to earth. 

 

 

 

 

Dimension 


mm (in) 

48.0 (1.89) 

131.5 (5.177) 
125.0 (4.921)

 

Distance 


 

mm (in) 

50 (2.0) 

100 (4.0)) 

 

 

FIG. 4 - MOUNTING / DISMOUNTING INSTRUCTIONS 

For DIN rail fastening according to IEC 60715 TH35-7.5(-15) 
Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between adjacent devices as specified in the 
Installation Instruction of each family.

 

MOUNTING: 

 

1.

 

Snap top (A) hangs on the rail top (B), adjust 
the product into vertical state, snap bottom 
(D) locates into the lower end of rail (C). 
 

2.

 

Install vertically. 
 

3.

 

Insert the copper wires into the top and 
bottom access points and fix them with a 
screwdriver. 
 

4.

 

Adjust the output voltage with a suitable tool 
according to adjustment range in the 
selection guide. 

 

 

 

 

DISMOUNTING: 

 

5.

 

Insert the screwdriver into E, pull down the 
snap and make it tilt outward in the 
meantime, then it can be removed from the 
rail. 

1.

 

 

 

 

 

 

 

Содержание LEC480 Series

Страница 1: ...one per evitare la riaccensione accidentale 3 Osservare tutte le normative locali e nazionali per garantire un cablaggio corretto 4 Non modificare o riparare questo prodotto 5 Non aprire il dispositivo poiché all interno sono presenti alte tensioni 6 Fare attenzione ad evitare che corpi estranei entrino nel guscio 7 Non utilizzare questo prodotto in luoghi umidi o aree in cui potrebbe verificarsi ...

Страница 2: ... SC overvoltage OV overtemperature OT Overload OL hiccup mode description When the power supply provides 105 150 of the rated output current there are two protection modes The power supply will first enter the hiccup protection mode at a certain overload current point The output overload current continues to increase and the product will enter the constant current hiccup mode due to different inpu...

Страница 3: ...l fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Snap top A hangs on the rail top B adjust the product into vertical state snap bottom D locates into the lower end of rail C 2 Install ver...

Страница 4: ... the European equivalent type Surge protection it is strongly recommended to provide external surge arresters SPD according to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 30 C to 70 C 20 90 r H non condensing UL Certified up to 50 C NOTES Data may change without prior notice in order to improve the product Please refer to the latest ve...

Отзывы: