BEL LDD240-WU Скачать руководство пользователя страница 5

 Asia-Pacific

+86 755 298 85888

Europe, Middle East

+353 61 225 977

North America

+1 408 785 5200

© 2017 Bel Power Solutions & Protection

BCG.00966_AA

LDD240-WU  

240 W Universal DC-DC Converter

5

4.2 OUTPUT VOLTAGE PROGRAMMING 

LDD240-WU output voltage can be programmed over a range from 4.5V to 55V thanks to the “Output Voltage” menu item, see §4. The 
resolution is 10 mV. 
While setting the output voltage the screen cycles between integer part (with dot point on) and cents of volts every 3sec. For example, if the 
value 24.56 V is set the screen cycles between the following two screens: 

Figure 4. Example of 24.56 V setting value shown on display 

4.3 CURRENT LIMITATION 

LDD240-WU can be set-up with 2 different current limitation algorithms, depending on application. The maximum current delivered by the 
device can be limited thanks to the “Output Current (IO)” menu. The maximum output current (Imax) can be limited from 1 A to 11 A (default 
10 A) through this menu, see §4. Once the load asks for more current than the programmed Imax the device goes into current limitation 
mode; two limitation algorithms are selectable by the user, see §3.3.1 and §3.3.2 for details. 
 
NOTE: To self-protect, the device never delivers higher current than the one specified on the datasheet “Output power limitation curve” and 
“Output current limitation curve” charts. This regardless of the Imax setting value. 

4.3.1 

HICCUP 

When LDD240-WU is set up in “Hiccup mode (HU)” the output current is limited at 1.5xImax. When the programmed Imax value is exceeded 
a timer is started. If the load current demand is not reduced below Imax within 5 seconds the output is switched off for 10 seconds.  
Overload (OL) error message is shown on the display, see §3.6 details. This cycle is then repeated until the load current demand is not 
decreased below Imax. 
This operating mode is recommended when powering loads requiring high inrush current demands.  In case of a direct short circuit on the 
output the output is switched off in about 0.2 seconds and kept off for 10 seconds. Short Circuit (SC) error message is shown on the display, 
see §3.6 details. This cycle is then repeated until the short circuit is removed. 
Note: when “Parallel (PA)” mode is selected the current limitation method is automatically fixed to “Constant Current (CC)” model and it is not 
possible to select “Hiccup mode” when “Parallel mode” is selected.  

4.3.2 

CONSTANT CURRENT 

When LDD240-WU is set up in “Constant Current (CC)” the output current is limited at Imax. If the load asks for more current than Imax the 
output voltage is progressively decreased to keep the output current regulated at Imax. When the output voltage decreases below 90% of the 
programmed output voltage the “DC-OK” relay dry contact opens see §3.5, informing the user that the output voltage is no more regulated. 
This operating mode is recommended when powering highly capacitive loads. In case of a direct short circuit on the output the output is 
switched off in about 0.2 seconds and kept off for 10 seconds. Short Circuit (SC) error message is shown on the display, see §3.6 details. 
This cycle is then repeated until the short circuit is removed. 

4.4 OUTPUT ENABLE 

The LDD240-WU is provided with a software control allowing to switching ON and OFF the output of the device. This flag is available at 
Modbus address 0x1014, see §3.7 for details. 

4.5 DC-OK RELAY

A normally open relay is used to indicate that the output voltage is available and regulated. If the output voltage drops below 90% of the 
programmed output voltage value.

Содержание LDD240-WU

Страница 1: ...USER MANUAL belfuse com power solutions LDD240 WU 240 W Universal DC DC Converter ...

Страница 2: ...1 Product description 3 2 Features and benefits 3 3 Functional description 4 3 1 Operating mode 4 3 2 Output voltage programming 5 3 3 Current limitation 5 3 4 Output enable 5 3 5 DC OK Relay 5 3 6 Alarms 6 3 7 Modbus 6 4 User interface 8 4 1 LOGS 9 5 Technical Specifications 9 ...

Страница 3: ...oltage is 90 of the programmed output voltage value 4 DC Input input voltage supply range is from 12 to 48 VDC 5 Display 2 digits LED display used to program the device and read its status 6 Control Keys 3 push buttons are provided to navigate through menus and to select various functions Figure 1 Front panel view 3 FEATURES AND BENEFITS Up to 240 W output power voltage dependent Converts any volt...

Страница 4: ...ode must be set to Single SI see 4 Any voltage between 11 VDC and 55 VDC can be converted in any voltage between 5 VDC and 55 VDC with a max output power of 240 W see datasheet for details 4 1 2 INPUT PROTECTION DEVICES Multiple LDD240 WU can be connected in parallel to increase the output power capabilities and or for redundancy purposes When operating in this mode operating mode must be set to P...

Страница 5: ...load OL error message is shown on the display see 3 6 details This cycle is then repeated until the load current demand is not decreased below Imax This operating mode is recommended when powering loads requiring high inrush current demands In case of a direct short circuit on the output the output is switched off in about 0 2 seconds and kept off for 10 seconds Short Circuit SC error message is s...

Страница 6: ...nusually high levels If no modification of the ambient operating temperature and or load conditions is performed by the user it is highly possible that an Over Temperature Ot error occurs leading to the output switch off 4 6 4 OVER TEMPERATURE ERROR The Over Temperature Ot error message appears when the internal temperature exceeds the safe limits In this case the output is switched off The output...

Страница 7: ...N MAX DESCRIPTION SETTINGS 0x1000 UINT16 R W 1 1 99 Modbus address 0x1010 UINT16 R W 0 01 4 5 57 Nominal output voltage V 0x1011 UINT16 R W 0 1 1 11 Maximal output current A 0x1012 UINT16 R W 1 1 2 Operating mode 3 1 1 Single 2 Parallel 0x1013 UINT16 R W 1 1 2 Current limitation 3 2 1 Hiccup Constant current 0x1014 UINT16 R W 1 0 1 Output enable 0 Disabled 1 Enabled METERING 0x2000 SINT16 R 0 1V 0...

Страница 8: ... the configuration menus During normal operation the measures are reported Alarms are also reported on the display The layout of the menu is shown below The various options are selected with the 3 keys Figure 5 HMI User can select the measure to show on the display pressing the set button as shown beside The 3 available measures are Output voltage Output current Input voltage Figure 6 HMI measures...

Страница 9: ...ot used Active when the output is short circuited 5 1 4 OUTPUT OVERLOAD Modbus address Value1 Value2 0x4003 Inactive 0 Active 1 Not used Active when the output is overloaded 5 1 5 USB POWERED Modbus address Value1 Value2 0x4004 Inactive 0 Active 1 Not used Active when the unit is powered by USB only 5 1 6 OVER TEMPERATURE WARNING Modbus address Value1 Value2 0x4005 Inactive 0 Active 1 Not used Act...

Отзывы: