background image

LDC240 Series

 

2

 

 

 

 

[email protected] 

 

 

USER INSTRUCTIONS

 

1) DESCRIPTION 

DIN rail mountable primary switched-mode power supply with 90 - 264 VAC (110 - 345 VDC) input, suitable for single phase mains line and DC line. 

2) INSTALLATION 

Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device 
is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).  
The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping. 
The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce 
the load (see Fig.8) 

3) CONNECTIONS

 

The device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power and 
waited for internal capacitors discharge (minimum 1 minute) 
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of: 
60°C for ambient up to 45°C 
75°C for ambient up to 60°C 
90°C for ambient up to 70°C 
Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5) 

4) INPUT PROTECTION

 

The device input is provided with varistors against overvoltage. Input is provided with internal fuses 6.3AT /250 VAC, thus an external short circuit / overcurrent protection 
must be provided by the end user (see Fig.6). 
For operation on a single-phase system, a protection fuse on the phase must be provided. 

Surge protection:

 it is strongly recommended to provide external surge arresters (SPD) according to local regulations. 

5) AC INPUT CONNECTION

 

The device can be connected to single phase AC line with rated Vin 120 - 240 VAC (see Fig.7). Please connect the PE first. 

6) DC INPUT CONNECTION 

Connect L terminal to (+) positive pole, N terminal to (-) negative pole and  

terminal to GND. Rated voltage 110 

 345 VDC. The device is also suitable for photovoltaic 

or wind turbine applications (see Fig.7). 

7) OUTPUT CONNECTION 

The device is suitable for 

SELV

 and 

PELV 

circuitry. Pay attention to LDC240-72 and LDC240-72P is not 

SELV

Vout can be adjusted with a potentiometer to a wide range (see Fig.1) 
Check Vout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal 
power. 

8) PARALLEL CONNECTION AND REDUNDANCY

 

Power supplies can be connected in parallel to increase power. For paralleling for power set the Ilim jumper to C.C. algorithm.  
Vout must be set uniformly (±100 mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution. 
Models with 

“P”

 suffix have an integrated ORing circuit. 

For redundant connection, use the Models 

“P”

 or an external isolating device must be used (see accessory device). 

9) OUTPUT PROTECTION 

The device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).

 

OL and SC:

 are controlled by a hiccup mode or a constant current (C.C.) mode protection with the following behaviour.

 

The Hiccup mode or C.C. mode are selectable with Jumper (see Fig.1) 
OL behaviour in hiccup mode:

 Max. OL = 1.5 x In the output voltage remains constant at nominal voltage for 5s and after that time the device starts an ON/OFF cycle.

 

OL behaviour in C.C. mode: 

the maximum output current is limited at 1.1 x In if the load resistance is further decreased the output voltage starts to drop. 

 

SC behaviour in hiccup mode:

 the device supplies 1.5 x In for 5 s, after that time it switches off for 10 s. The ON/OFF cycle is repeated continuously. 

 

SC behaviour in C.C. mode:

 the device supplies 1.1 x In continuously into the short circuit without switching off  

 

Output OV circuit protection

: the output is protected against potential OV due to internal malfunction or coming from the load for  

Vout 

 

 Vnom x 1.2 

 1.3, depending on the model. 

 

OT protection:

 turns off the device if the internal temperature exceeds a safe limit. 

The device restarts automatically after cooling down. To recover to normal operation, reduce air temperature surrounding the power supply, increase cooling or reduce 
load (see Fig.8). 

10) FEEDING DC MOTORS 

It is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can trigger 
overcurrent protection (see accessory device). For these applications the C.C. (Constant Current) mode of current limitation is recommended.

 

NOTE:

 motors can generate high conducted noise on the DC line. Therefore, it is not recommended to feed on the same line motors and equipment sensitive to noise. 

11) OPERATION WITH BATTERY 

When a battery is connected in parallel to the Output for backup purposes; the LDC240 must be set on C.C. mode to avoid battery over-charging (see accessory device). 

 

 

Содержание LDC240 Seriesl LDC240-12

Страница 1: ...ant de l utilisation des produits CAUTION ACHTUNG ATTENZIONE AVVERTISSEMENT RISK OF BURNS EXPLOSION FIRE ELECTRICAL SHOCK PERSONAL INJURY Never carry out work on live parts Danger of fatal injury The product s enclosure may be hot allow time for cooling product before touching it Do not allow liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the dev...

Страница 2: ...de range see Fig 1 Check Vout before connecting the power supply to the load With output voltage set to the max value the continuous current x voltage must not exceed the nominal power 8 PARALLEL CONNECTION AND REDUNDANCY Power supplies can be connected in parallel to increase power For paralleling for power set the Ilim jumper to C C algorithm Vout must be set uniformly 100 mV on each power suppl...

Страница 3: ...e L Positive DC N Negative DC Earth ground Output Positive DC Negative DC Dry contact NC Dimension W D H mm inc 40 1 57 110 4 33 115 4 52 Distance A B mm inc 20 0 8 100 3 9 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between ad...

Страница 4: ...ng to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 70 C No derating NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of the Installation Instruction for each product by visiting belfuse com power solutions ACCESSORIES LDX...

Отзывы: