Operation METPOINT® BDL compact
48
METPOINT® BDL compact
14.3.2.8 Configuration of analogue sensors
Use only for the METPOINT
®
BDL compact. Variants with an assembled analog board are possible.
Short overview of the possible
Type
settings including examples. For
BEKO-Digital
, see Chapter
12.2.2.1
Selection of the sensor type (example BEKO-Digital sensor type)
and
12.2.2.6
Dew point
sensor with the BEKO-DIGITAL type
.
The
alarm settings,
recording
buttons, the
resolution
of the decimal places as well as the
short name
and
value name
are all described in Chapter
12.2.2
Sensor settings
.
For the marking of the text fields, see Chapter
12.2.2.7
Marking and setting text fields
!
14.3.2.8.1 Type 0/4 – 20 mA
Main menu
Settings
Sensor settings
B1
Type text field
0-20 mA
Main menu
Settings
Sensor settings
B1
Right arrow (2
nd
page)
Scaling of the sensor (here, for example,
type
0 – 20 mA
- corresponds to 0 – 25 bar) can be
found in the data sheet of the connected sen-
sor.
e.g. SP21
For
scale 4 mA
,
please enter the lower scale
value and for
scale 20 mA
the upper scale
value.
The
ext. sensor supply voltage
is switched on
when the sensor requires this.
Please confirm with
OK.
Содержание METPOINT BDL compact
Страница 1: ...EN English Instructions for installation and operation Data logger METPOINT BDL compact 10 089 ...
Страница 15: ...Dimensions METPOINT BDL compact 15 Cutout for the mounting of the instrument panel ...
Страница 83: ...Operation METPOINT BDL compact METPOINT BDL compact 83 Info Status ...
Страница 84: ...Operation METPOINT BDL compact 84 METPOINT BDL compact Actual Values ...
Страница 102: ...Declaration of conformity 102 METPOINT BDL compact 18 Declaration of conformity ...
Страница 105: ...METPOINT BDL compact 105 ...
Страница 106: ...METPOINT BDL compact ...
Страница 107: ...METPOINT BDL compact 107 ...