9.4.3 Alarm enable:
EnbL
This function allows the alarm to be enabled or
disabled without altering any of the alarm parameters.
Using the
&
or
*
push button select
AL1
or
AL2
from the configuration menu and press
(
to reach
EnbL
in the alarm sub-menu. Pressing
(
will then
reveal the existing setting. The function can be
changed by pressing the
&
or
*
push button
followed by the
)
button to return to the alarm sub-
menu.
9.4.4 Type of alarm:
tYPE
Alarm 1 and Alarm 2 are totally independent, both
may be rate or total alarms, or one may be
conditioned for rate and the other for total.
Using the
&
or
*
push button select
tYPE
from
the selected alarm sub-menu and press
(
to
check or change the function. The
&
or
*
push
button will toggle the selection between
rAtE
and
totAL
, when set as required press the
)
button to
return to the alarm sub-menu.
Note:
When
tYPE
is changed, the alarm
configuration is automatically reset to the
default values and the alarm is disabled. It
must therefore be reconfigured before use.