6.  CONFIGURATION EXAMPLE

In this example a BA514G Tachometer is connected to
a  proximity  detector  producing  105  pulses  per
revolution.

The BA514G is required to display rotational speed in
RPM  with  a  resolution  of  one  RPM.    The  run-time
clock  is  to  operate  when  the  shaft  speed  exceeds
5  RPM.  The  display  is  to  be  updated  twice  per
second.

For this application the  operator needs  to reset the
run-time display to zero from the display mode, but
should not be able to reset the grand total run-time
from  the  display  mode.    To  prevent  tampering  the
instrument configuration menu is to be protected by
security code of 1209.

6.1  Configuration procedure

The BA514G Tachometer may be configured on-site
without disconnection from the power supply or from
the proximity detector.

Step 1

Enter the configuration menu

Enter  the  configuration  menu  by
simultaneously  pressing  

(

 and  

)

.

Assuming a security code has not already
been entered the instrument will respond
by  displaying  

inPut

  which   is   the   first

function  in  the  configuration  menu.    See
Fig 7.

Step 2

Select the type of input & debounce

With  

inPut

 displayed press  

(  

which will

reveal the sub-menu.   Using the 

&

 or 

*

button  select  

inP

 

.

 

tYPE

  and  press  

(  

to

reveal the current input.   The Tachometer
is  required  to  work  with  a  proximity
detector  so  again  using  the  

&

 or  

*

button  select  

Pr.

 

dEt

 followed  by  

)  

to

return to the  

inP

 

.

 

tYPE

 prompt in the sub-

menu.
Using  the  

&

 or  

*

 button  select

dEbouncE

  from  the  sub-menu  and  press

(

.  Using  the  

&

 or  

*

 button  select

dEFAuLt

 which will provide moderate pulse

edge noise protection.  If the Tachometer
is  subsequently  found  to  miscount  the
noise  rejection  can  be  increased.    Enter
the  selection  and  return  to  the  

inPut

prompt  in  the  configuration  menu  by
pressing the 

button twice.

See 5.4, 5.5 and 5.6

Step 3

Select  the  interval  between  display
updates

Using the  

&

 or  

*

 button select  

uPdAtE

in the configuration menu and press 

to

reveal  how  frequently  the  Tachometer
display is updated.

Using the  

&

 or  

*

 push button select

0

 

.

 

5

 (0.5  seconds  i.e. 2  display  updates

per  second).    Enter  the  selection  and
return  to  the  

uPdAtE

 prompt  in  the

configuration  menu  by  pressing  the  

)

button.
See 5.7

Step 4

Run-time display 

Using the 

&

 or 

*

 button select 

di5P-2

in the configuration menu and press  

(

to select if the run-time display is  

on

 or

oFF

.    The  Tachometer  is  required  to

display run-time therefore using the  

&

or  

*

 button select  

on

 and press  

)  

to

enter  the  selection  and  return  to  the

di5P-2

 prompt in the configuration menu.

See 5.8

Step 5

Position  of  decimal  point  in  speed
display.

Select  

dP

  from  the  configuration  menu

and press 

(

. The speed display will be

activated   and   identified   by   the   Rate
annunciator.  Using the  

&

 or  

*

 push

button position the  decimal point to the
right of the least significant digit to give a
total display resolution of 1.
Finally press the  

)  

button to enter the

selection and return to the  

dP

 prompt in

the configuration menu.

See 5.9

Step 6

Enter the speed scale factor

5CALE.5

  is  a  dividing  factor  adjustable

between 0.0001 and 99999 that enables
the Tachometer  to display  speed  in  the
required  engineering  units.    The  speed
display  timebase  is  determined  by

t-bA5E

 that is adjusted in Step 7.

In  this  example  the  Tachometer  speed
display  is  required  in  revolutions  per
minute.  The proximity detector produces
105  pulses  per  revolution  therefore

5CALE

 

.

 

5

 should therefore be adjusted to

105.0.

Using the  

&

 or  

*

 push button select

5CALE.5

  from  the  configuration  menu

and press 

to reveal the existing value

with one digit flashing.  This should be
changed   to   105.0   using   the  

&

 or  

*

push  button  to  adjust  the  flashing  digit
and the  

(  

button to transfer control to

the next digit and to position the decimal
point.  Finally, enter the new value and
return  to  the  

5CALE

 

.

 

5

  prompt  in  the

configuration menu by pressing 

)

.

See 5.10

22

Содержание BA514G

Страница 1: ...Issue 4 9th July 2019 BA514G General Purpose Tachometer Issue 4...

Страница 2: ...ed scale factor 5CALE 5 5 11 Timebase t bA5E 5 12 Display filter FiLtEr 5 13 Clip off CLP oFF 5 14 Local reset LoC clr 5 15 Local run time reset clr tot 5 16 Local grand total run time reset clr gtot...

Страница 3: ...7 Alarm output status no nC 8 4 8 Hysteresis H5tr 8 4 9 Alarm delay dELA 8 4 10 Alarm silence time 5IL 8 4 11 Flash display when alarm occurs FL5H 8 4 12 Access Setpoint AC5P 8 4 13 Adjusting alarm s...

Страница 4: ...4...

Страница 5: ...ter The instrument can accept pulses from most types of sensor and display speed per second minute or per hour plus run time in hours on a separate display The BA514G has a single pair of input termin...

Страница 6: ...ter may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 8 4 12 and 8 4 13 2 3 Displays The BA514G has two digit...

Страница 7: ...t fall below the lower threshold and rise above the upper threshold Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Ma...

Страница 8: ...pulse input ranges are selectable in the BA514G Tachometer configuration menu VoLt5 L and VoLt5 H The Tachometer input terminals 5 and 6 may be connected to any voltage pulse output sensor The BA514G...

Страница 9: ...erconnecting cable screens The BA514G Tachometer may be pipe mounted using a BA393G pipe mounting kit or panel mounted using a BA394 or BA395 panel mounting kit All are available as accessories 4 2 In...

Страница 10: ...ment is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as an acces...

Страница 11: ...r that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the monitored...

Страница 12: ...n or oFF See section 5 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 5 9 5CALE 5 Speed scale factor 5CALE 5 is a...

Страница 13: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...lse has noisy edges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachom...

Страница 17: ...shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The u...

Страница 18: ...ing used it is not necessary to enter a clip off value see 5 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The...

Страница 19: ...onfirmed by entering 5urE using the or button to adjust the flashing digit and the button to move control to the next digit Pressing will then reset the grand total to zero and return the Tachometer t...

Страница 20: ...ulse current flows through resistor R1 The current flowing in the circuit is determined by R1 which should be chosen to limit the pulse output current to less than 10mA For a 24V supply R1 should be g...

Страница 21: ...elect diVidE in the pulse output sub menu and press which will reveal the existing divisor The selected divisor can be changed by pressing the or push button followed by the button to return to diVidE...

Страница 22: ...between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 second...

Страница 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 24: ...ts unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the se...

Страница 25: ...nfigure clip off See 5 13 Alarms do not function Alarms have been disabled following calibration change Re enable both alarms See 8 4 3 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE...

Страница 26: ...single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a normally open or closed output An alarm delay a...

Страница 27: ...ur5salarm is activated when the speed or run time display equals the setpoint Note 5P15 is displayed for a speed alarm and 5P1H for a run time alarm See section 8 4 5 HI LO Alarm function Defines whet...

Страница 28: ...28...

Страница 29: ...eturn to the Hi Lo prompt in the alarm sub menu 8 4 7 Alarm output status no nC Each single pole alarm output may be open or closed in the non alarm condition When the BA514G power supply is turned of...

Страница 30: ...out having access to the configuration and alarm sub menus Protection against unauthorised or accidental adjustment is provided by a separate security access code Using the or push button select AC5P...

Страница 31: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Страница 32: ...en a Tachometer is supplied with an optional 4 20mA output the configuration menu is extended as shown in Fig 15 The 4 20mA output sub menu is accessed via the 4 20 oP function The 4 20mA output is co...

Страница 33: ...s function Using the or push button select 20 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or...

Отзывы: