![BEKA BA484DF Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/beka/ba484df/ba484df_manual_2723935024.webp)
24
HAZARDOUS (CLASSIFIED) LOCATION
UNCLASSIFIED LOCATION
EQUIPMENT
LOCATION
HAZARDOUS
NON
SEE NOTE 1
A9
ALARM
ALARM
OPTIONAL
OPTIONAL
A12
A11
A10
2
1
BA484DF or
BA488CF
SEE NOTE 6 & 7
S7
BA484DF LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class II, Division 2, Groups E, F & G
Class III
Class I, Zone 2, Groups IIC
BA488CF LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class I, Zone 2, Groups IIC
SEE
NOTE 4
SEE
NOTE 2
A7
OPTIONAL
ALARM
A8
A5
OPTIONAL
ALARM
A6
A3
OPTIONAL
ALARM
A4
A1
OPTIONAL
ALARM
A2
S6
S5
S4
S3
S2
S1
SEE NOTE 5
OPTIONAL
EXTERNAL
SWITCHES
BA484DF and BA488CF
Maximum input and
output parameters
Terminals 1 & 2
Vmax = 32V dc
NIFW Vmax = 17.5V (FNICO)
Ci = 1nF
Li = 8µH
These terminals comply with
The Fieldbus Nonincendive
Concept (FNICO) defined by
IEC 60079-27
(Typical current consumption
25mA)
Terminals S1 to S7
(combined parameters)
Vmax = 0V Voc = 14.7Vdc
Isc = 146.7mAdc
Co = 0.08µF
Lo = 1.1mH
Terminals A1 & A2; A3 & A4;
A5 & A6; A7 & A8; A9 & A10
and A11 & A12
Vmax = 32V dc
Ci = 0.04µF
Li = 0.02mH
FI
E
L
D
B
U
S
SEE NOTE 9
SEE NOTES
3A and 3B
SEE
NOTE 10
Содержание BA484DF
Страница 1: ...Issue 8 8th May 2006 BA488CF Intrinsically safe Panel mounting Fieldbus Display Issue 8...