Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450oC

T2

300oC

T3

200oC

T4

135oC

At an ambient temperature between –40 and
+70

o

C.

Note: minimum guaranteed operating temperature
is –20ºC.

3.3   Fieldbus connection
The  BA448CF-P  Indicator  is  powered  and
communicates via the fieldbus, which is connected
to  terminals  1  and  2.      These  are  non-polarised,
comply with the Fieldbus Intrinsically Safe Concept
(FISCO)  defined  in  EN  60079  Part  27  and  have
separate entity parameters shown below:

                          FISCO                  Entity

Ui

=

17.5V dc

22.0V dc

Ii

=

380mA dc

250mA dc

Pi

=

5.32W

1.2W

The 

maximum 

equivalent 

capacitance 

and

inductance at terminals 1 & 2 is:

Ci

=     0

Li

=     8µH

3.4 Certification Label Information
The certification information label is fitted to the top
outer surface of the enclosure.  It shows details of
the  ATEX  certification  and  a  statement  that  the
instrument  is  a  FISCO  Field  Device,  plus  BEKA
associates  name  and  location.  IECEx  approval
information  is  also  included.    The  label  may  also
contain non-European certification information.
The  instrument  serial  number  and  year  of
manufacture are shown on the rear panel adjacent
to the terminals.

4.  SYSTEM DESIGN FOR HAZARDOUS
     AREAS

4.1  FISCO Systems
The  BA448CF-P  may  be  connected  to  any  ATEX
certified  FISCO  compliant  fieldbus  segment,
providing  the  segment  can  supply  the  additional
13mA required to power the instrument.

Fig 1 shows a typical fieldbus segment.  To comply
with  FISCO  requirements,  the  power  supply,
terminators,  field  devices  and  the  interconnecting
cables must conform to EN 60079 part 27.

Fig 1   FISCO fieldbus system

4.2  Non-FISCO Systems
For  non-FISCO  applications  the  BA448CF-P
Fieldbus  Indicator  has  a  higher  voltage  entity
intrinsic safety input parameter allowing connection
to a wide range of fieldbus segments.

The  BA448CF-P  Fieldbus  Indicator  may  be
connected  to  any  intrinsically  safe  segment
providing:

The device powering the fieldbus segment is
ATEX  certified  and  has  output  parameters
equal to or less than:

Uo

=

22V dc

Io

=

250mA dc

Po

=

1.2W

The  segment  can  provide  an  additional
13mA to power the Fieldbus Indicator.

Note:  The equivalent capacitance Ci of the
BA448CF-P  Fieldbus  Indicator  is  zero  and
the  equivalent  inductance  is  insignificant.
Therefore 

these 

BA448CF-P 

safety

parameters do not need to be considered.

Содержание BA448CF-P

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA448CF P...

Страница 2: ...Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel...

Страница 3: ...Issue 2 23 rd June 2011 BA448CF P PROFIBUS PA Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 2...

Страница 4: ...ured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal point position 6 4 9...

Страница 5: ...es to this manual For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is available from the BEKA sales office or may be downloaded...

Страница 6: ...on information The instrument serial number and year of manufacture are shown on the rear panel adjacent to the terminals 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 FISCO Systems The BA448CF P may be con...

Страница 7: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Страница 8: ...the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will...

Страница 9: ...BA448CF P listener are not known In the SCAn function pressing the P button causes the BA448CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal...

Страница 10: ...8...

Страница 11: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input...

Страница 12: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Страница 13: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph dis...

Страница 14: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus nod...

Страница 15: ...y mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Страница 16: ...a scale for the horizontal bargraph 8 2 Tag number The BA448CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 8 3 BEKA PROFIBUS PA Display Fieldbus...

Страница 17: ...SCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and Canada providing the fieldbus...

Страница 18: ...16...

Страница 19: ...17...

Страница 20: ...18...

Страница 21: ...19...

Страница 22: ...20...

Страница 23: ...21...

Страница 24: ...22...

Страница 25: ...BA448CF P may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...