77
Step 7
Adjust the display filter
The speed display filter parameters
should be adjusted experimentally after
installation to provide a stable speed
display with an acceptable step
response.
During commissioning it is recommend
that initially the second digit of the filter
parameters is set to 0 (step response
off) and the first digit (amount of
filtering) is adjusted to provide
acceptable speed display stability. The
second digit should then be increased
until acceptable speed display stability
is once again achieved.
To adjust the filter parameters select
‘FILtEr’ from the main menu and press
P
to reveal the current setting. The first
digit will be flashing and may be
adjusted using the
Up
or
Down
button.
The
P
button will transfer control to the
second digit. When both are set as
required, return to the ‘FILtEr’ prompt in
the main menu by pressing
E
.
Note:
While adjusting the filter, the speed is
shown on the lower display so that
stability can be assessed.
Step 8
Turn the run-time display on
In this example the run-time display is
required so the lower display must be
switched on.
Select ‘dISPLAY.2’ from the main menu
and press
P
which will reveal if it is
turned ‘On’ or ‘OFF’. Using the
Up
or
Down
button toggle the display to ‘On’
and press E to return to the
‘dISPLAY.2’ prompt.
Step 9
Define the clip off threshold
The run-time display is required to
operate when rotational speed exceeds
5rpm. Select ‘CLIP-OFF’ from the
main menu and press
P
which will
show the current value with one digit
flashing. Using the
Up
and
Down
buttons to adjust each digit in turn and
the
P
button to transfer control between
digits, enter 5 Finally return to the
'CLIP-OFF' prompt in the main menu by
pressing
E
.
Step 10 Turn local reset on
In this example the operator is required
to zero the run-time display from the
instrument front panel. The local reset
function should therefore be turned on.
Select ‘LOC-rSEt’ from the main menu
and press
P
which will reveal if it is
turned ‘On’ or ‘OFF’. Using the
Up
or
Down
button toggle the display to ‘On’
and press E to return to the ‘LOC-rSEt’
prompt.
Step 11 Reset the run time grand total
Before completing commissioning the
grand total run time should be reset to
zero. Select 'CLr.Gtot' from the main
menu and press
P
which will cause the
instrument to display 'Clr. no'. Toggle
this to 'CLr. YES' using the
Up
or
Down
push-buttons and press
P
which will
result in a '0000' prompt. Using the
Up
,
and
Down
buttons and the
P
button to
move to the next digit, confirm the
request by entering the password
'SurE'. Note: S is entered as 5.
Pressing
E
will then reset the grand
total counter to zero and return the
instrument to the 'CLr. Gtot' prompt in
the main menu.
Step 12 Define the security code
Defining a security code prevents
unauthorised access to the programme
functions. Select 'COdE' from the
main menu and press
P
which will
reveal the existing security code. Using
the
Up
and
Down
buttons enter the new
code 1209 digit by digit. The
P
button
will transfer control between digits.
When the new code has been entered,
press
E
to return to the main
programme menu.
Step 13 Return to the display mode
Following completion of programming
and calibration, return the BA368C to
the display mode by pressing
E
. All the
programming functions will now be
stored in permanent memory and will
be protected from accidental or
unauthorised adjustment by the
security code.
Содержание BA368C
Страница 12: ...12 ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 ...
Страница 20: ...20 ...
Страница 28: ...28 ...
Страница 34: ...34 ...
Страница 44: ...44 ...
Страница 52: ...52 ...
Страница 67: ...67 ...
Страница 72: ...72 ...
Страница 80: ...80 ...
Страница 87: ...87 ...