BEINAT SGM600 Скачать руководство пользователя страница 7

Page  7

Gas  imput  Test

WARNING! Actions to be taken in case of alarm

Gas
1) P
ut out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide

or by an excess

or  deficiency  of  oxygen

N O T E S

The  installation  of  the  SGM600  probe,  its  ordinary  and
extraordinary maintenance, and its out of service removal at
the end of the functional life guaranteed by the manufacturer,
must be carried out by authorized or specialized personnel.

The general test should be performed by issuing gas from a pre-
calibrated  aerosol within the  percentages  illustrated on the
side.

Important: 

This test must be carried out at least once a year.

Gas

TEST  SGM600

with  pre  calibrated  gas  bottle
at  20%  of  LEL    ±2%

            For GAS

Methane
LPG
Hydrogen
Ammonia-explosiv
Acetylene
Gasoline vapors
Alcohol

Содержание SGM600

Страница 1: ...mperature environments avoiding false alarms due to anomalous events The probe has a 0 20 LEL linear output conforming to the 4 20mA standard for which can be connected with one of BEINAT s industrial control units The important innovation of this probe is The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having to send to BEINAT Srl CONF...

Страница 2: ...ECTATIONS The installation of the SGM600 Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Страница 3: ... IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Collector Wall 8 IP65 M...

Страница 4: ...ethane Hydrogen Ammonia Acetylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data 30 cm Heavy gases...

Страница 5: ...ons 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 K1 K2 K3 Connettore a innesto montato su sonda Led ON connection USB port Selec operation range FUNCTIONING OF LED The integrated LED on the sonde has a threefold function 1 Green LED Normal operation In waiting phase the LED flashes 2 Red LED State of alarm The frequency of light changes according to the percentage of gas monitored 3 Le...

Страница 6: ...at the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX...

Страница 7: ... a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid station and inform the operators that you could have been poisoned by Carbon Monoxide or by an excess or deficiency of oxygen NOTES The installation of the SGM600 probe its ordinary and extraordinary maintenance and its out of service removal ...

Страница 8: ...UIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ...

Отзывы: