background image

Page  7

Gas  imput  Test

The  installation  of  the  SGM595/A  probe,  its  ordinary  and
extraordinary maintenance, and its out of service removal at
the end of the functional life guaranteed by the manufacturer,
must be carried out by authorized or specialized personnel.

The general test should be performed by issuing gas from a pre-
calibrated  aerosol within the  percentages  illustrated on the
side.

Important: 

This test must be carried out at least once a year.

Gas

TEST  SGM595/A

with  pre  calibrated  gas  bottle
at  20%  of  LEL    ±2%

            For GAS

Methane
LPG
Hydrogen
Acetylene
Gasoline vapors
Alcohol

WARNING!    Actions  to  be  taken  in  case  of  alarm

1)  Put  out  all  free  flames.
2)  Close  the  main  gas  tap  or  the  LPG  cylinder  tap.
3)  Do  not  turn  any  lights  on  or  off;  do  not  turn  on  any  electrical  device  or  appliance.
4)  Open  windows  and  doors  in  order  to  increase  ventilation.
If  the  alarm  stops,  its  cause  must  be  found  and  the  relevant  consequent  measures  taken.
If  the  alarm  continues  and  the  cause  of  gas  presence  cannot  be  found  or  removed,  abandon  the  building
and  call  the  emergency  services  when  outside  (fire  department,  distributors,  etc.)
IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a
sufficient  concentration  to  activate  the  general  alarm.

Warning  !!

If  you  have  the  following  symptoms:  vomiting,  sleepiness,  or  else,  go  to  the  closest  first  aid
station  and  inform  the  operators  that  you  could  have  been  poisoned  by  Carbon  Monoxide,  or
by  an  excess  or  deficiency  of  oxygen

Test  after  replacing  the  sensor.

Reconnect  the  power,  the  probe  starts  blinking  to  the  waiting  time  (Warm-up).
After  waiting  you  can  proceed  to  test  the  functioning  inputting  the  sample  gas.
WARNING !!  From  this  moment  on  for  all  the  duration  of  24  hours  of  self-calibration,  the  probe  must  stay  in
clean  air  without  loss  of  GAS.

The  probe  continues  to  blink  at  a  low  frequency  again  for  24  hours  to  make  sure  that  the  probe  do  the  auto
calibration.

Before  performing  this  operation  disconnect  the  power  to  the  probe

Maintenance  and  gas  sensor  replacement

Probe  with  sensor

                   Probe  with sensor

            Sensor

Probe  with      sensor

to  be  raplaced

                 removed

            remounted

Содержание SGM595/A

Страница 1: ...rotection that together with one of BE INAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen and other types of gas The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maxi...

Страница 2: ...TATIONS The installation of the SGM595 A Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Страница 3: ...ed personnel Side View 60 mm 80 mm 80 mm Rearward View Foro 6 5 mm 100 mm 100 mm 40 mm Front View CONTROLUNITS MOUNTING PROBES Max DEGREE PRE ALARMS POSITIVE OPERATING protec alarms safety range GS100M unit 1 zone Wall cabinet 1 I P 4 4 2 1 Y E S N O GS300M unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O GS300 Mc unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O BX444 MC unit 1 zone Wall cabinet 4...

Страница 4: ...ow The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Main Alarm Relay Optional Relay Board CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the jum...

Страница 5: ...irectly WARNING These measurement should be performed in clean air Moreover this test must be performed only with the probe connected to a control unit or with a 220 Ohm resistance installed between terminal 2 and terminal 3 Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC Voltmeter Power Supply 12 24 V Troubleshooting before calling a technician Display legend Displays the type of probe or device Dis...

Страница 6: ... controlled boiler burner industrial kitchens etc but on the opposite side 2 The probes must not be affected by fumes vapors and by sources of moving air which could distort the detection 3 The probes must not be installed near sources of heat fans or vacuum cleaners NOTE Recall that the GAS detection sensors placed inside the probe are perishable components whose average duration is variable 5 ye...

Страница 7: ...e of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid s...

Страница 8: ...es points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natur...

Отзывы: