BEINAT SG895 Скачать руководство пользователя страница 5

Page  5

3    2    1

R

Linear  Output    4-20  mA

Power  Supply
    12÷24  V.

1    2     3   4    5    6

Fault  Relay

C

N O

C

N O

C

N O

Opiional  Relay  Board     

CARD03

 K3                K2                K1

Relay  20%  LEL

Relay  13%  LEL

Warning  !!
Before  to  do  this,  it  may  want  to  check  the  operation  range  of  the  control  unit.

OPTIONAL  CARD03  BOARD  INSERTION

Before  inserting  the  Open  Collector  CARD03
board,  switch  off  the  power  to  the  probe.

Insert  the  board  according  to  the  drawing
keeping  the  terminal  block  on  the  left.

All  relays  are  voltage  free.
Contact  capacity  1A    SELV

SELECTION  OF  THE  OPERATING  RANGE

The  conventional  probes  leave  the  factory
with  the  operating  range  is  selected  to  20%
of  the  LEL

To  select  the  operating  range  to  100%  LEL
you  need  to  move  the  jumper  between  the
central  and  the  top  pole.

Electrical  cabling
Please  read  the  paragraph:  “Particular  Specifications  for  Use  in  Explosive  Atmospheres
in  conformance  with  the  European  Directive  ATEX  2014/34/UE”

.

NOTE:
Please  remind  that  if  you  pierce  the  FLAMEPROOF  container,  it  will  completely  lose  its  properties.
Moreover,  you  should  install  a  FLAMEPROOF  cable-gland  for  the  connection  cables

Selec.  operating  range

Led  ON

connection  USB  port

Led  ON

connection
USB  port

SG895 Explosive Gas                                                       SG895 Toxic Gas

FUNCTIONING OF LED
The  integrated  LED  on  the  probe  has
a  threefold  function:
1)  Green  LED.  Normal  operation;  In
waiting  phase,  the  LED  flashes.
2)  Red  LED.  State  of  alarm;  The
frequency  of  light  changes  according
to  the  percentage  of  gas  monitored.
3)Led  yellow.  The  probe  detects  an
anomal y,  FAULT

FUNCTIONING OF LED
The integrated  LED on the   probe has
a  this  functioning:
1)  Green  LED.  Normal  operation;

3    2   1

1
2
3
4
5
6
7

1
2
3
4
5
6
7

1
2
3
4
5
6
7

1
2
3
4
5
6
7

ON

1  2  3  4  5   6

K3       K2       K1

20%

100%

Electrical connections

Содержание SG895

Страница 1: ...the home fitness concept The device has the capacity of controlling through its Catalytic technology sensors the presence of Explosive Gases TOXIC GAS such as Carbon Monoxide see table on page 5 Thanks to its innovative technology advances the probe is suitable to industrial use and car parks The probe is managed by a microprocessor which not only supplies an alarm signal to the Control Unit conne...

Страница 2: ...ation or installation can damage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the probe could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Absolutely avoid using any cloth dipped in thinners alcohol and chemical detergents Power supply 12 24 VDC 10 Power demand 90 mA in functi...

Страница 3: ...ould be grounded and connected to the external or internal terminal that must be protected against corrosion The user should regularly clean the product in order to avoid any dust accumulation on its walls The sensors should be installed mechanically so that the detection cell is facing down If the connections are located in a classified zone they should be protected in certified cases 65 mm 100 m...

Страница 4: ...m the highest point of the ceiling in order to detect Volatil gases CO The probe should not be installed near the appliance to be controlled but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort its measurement It should be located away from sources of heat ventilators or fans Technical specifications of the gas detection capsules Positioning ofthe pro...

Страница 5: ...abling Please read the paragraph Particular Specifications for Use in Explosive Atmospheres in conformance with the European Directive ATEX 2014 34 UE NOTE Please remind that if you pierce the FLAMEPROOF container it will completely lose its properties Moreover you should install a FLAMEPROOF cable gland for the connection cables Selec operating range Led ON connection USB port Led ON connection U...

Страница 6: ...m A Linear 5 Fault Zone 9 3 12 14 6 17 3 Output in mA Clean Air 300 ppm CO 100 ppm CO 50 ppm CO 30 ppm CO Time in minutes Diagram detection time mA Referred to the CO gas Current Voltage Conversion Graph with 220 Ohm Load Resistance 0 4 5 10 15 20 V m A 0 88 1 1 2 2 3 3 4 4 Linear 5 0 50 100 150 200 250 10 Toxic Gas Detection diagram Warning for gas chlorine range 0 10 ppm PowerSupply 12 24 V Line...

Страница 7: ... of Beinat s r l should be contacted directly Maintenance Troubleshooting before calling a technician The overall testing and the ordinary or extraordinary maintenance It must be carried out every six months by emitting gas from a pre calibrated bottle within the percentages of test plate of the probe To perform a perfect test connect the tester TS1008 to the USB port and emit the agas from the pr...

Страница 8: ...al city office your household waste disposal service or the shop where you purchased the product Attention in some countries of the European Union the product is not included in the field of application of the National Law that applies the European Directive 2002 96 EC and therefore these countries have no obligation to carry out a separate collection at the end of life of the product WARRANTY The...

Отзывы: