Page  2

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper,
and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible
damages caused to people, animals or objects.

TERMS and EXPECTATIONS: The installation of the SG500 Probe, its ordinary and extraordinary maintenance, every
six months, and its out of service removal at the end of the functional life guaranteed by the manufacturer, must be
carried out by authorized or specialized personnel.

Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levels of humidity.

Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.

Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.

Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.

Technical  Specifications

Precautions

Power Supply   .................................................................................................... 12÷24VDC           ± 10%
Power Demand

 ................................................................................................ 110 mA  max @  13.8V

Sensor  ....................................................................................................................................... Catalytic
Sensor range of measurement  ...................................................................................... 0 -  100% of L.E.L.
Detector range of measurement  .....................................................................................  0 ÷ 20% of L.E.L.
Detection    .................................................................................................................  Gas  Methane,  LPG
Output ........................................................................................................ 4mA - 20mA standard tolerance
Accuracy    ................................................................................................................................  +/-  1%
Long  term  shift  in  clean  air      .....................................................................................................  <  ±  3
LELWarm-up time...................................................................................................................... 1,5 minutes

Control units that can be used ............ BX444-Mc, BX449F, GS100M, BX280, BX180, GS300Mc, BX316xp, BX308xp
Functioning Humidity  ................................................................................................. 0-90% non condensed
Functioning  Temperature    ................................................................................................  –10°C  to  +50°C

Max.  distance  between  probe  and  unit    ...........................................................................................  100  m
Connection  cables  diameter    ...........................................................................................................  1mm
Connection: The probe connection cables should not be laid with the supply cables
If the cables are laid together with power cables, you must use a shielded cable

Probe’s body material  ............................................................................................... ABS self-extinguishing
Degree  of  external  protection    .........................................................................................................  IP30
Electromagnetic compatibility “CE Reference Norms”  ..................................................................... EN 50270
Size  ........................................................................................................................................ 110x35x55
Degree  of  external  protection    .........................................................................................................  IP30

WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 50 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year,  by a  qualified
technician.

Technical Features  SG500

Code

 

         Type of Gas

                      Sensor

               Working range           Temperature

SG500met

Methane

        Catalytic

    LEL 0-100%

-10+50°C

SG500lpg

LPG

        Catalytic

    LEL 0-100%

-10+50°C

Содержание SG500

Страница 1: ...70 Compliant EN 60079 29 1 Installation EN 60079 29 2 Reports issued by TUV Italia Channel Beinat gas solutions Electric connections also available on Conventional Gas Sensor SG500 V 3 The SG500is born from the elegance and prestige that has always distinguished BEINAT S r l and from the home fitness concept The probe is a Catalytic gas detection unit with IP30 protection that together with one of...

Страница 2: ...ge of measurement 0 100 of L E L Detector range of measurement 0 20 of L E L Detection Gas Methane LPG Output 4mA 20mA standard tolerance Accuracy 1 Long term shift in clean air 3 LELWarm up time 1 5 minutes Control units that can be used BX444 Mc BX449F GS100M BX280 BX180 GS300Mc BX316xp BX308xp Functioning Humidity 0 90 non condensed Functioning Temperature 10 C to 50 C Max distance between prob...

Страница 3: ...unit 1 zone Wall cabinet 4 IP44 2 1 YES NO BX150 unit 1 zone Panel 1 IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308xp unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308xp Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316xp unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316xp Bo...

Страница 4: ...point of the ceiling in order to detect light gases Methane etc The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans 30 cm Light Gases 30 cm Heavy Gases ...

Страница 5: ...is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Electrical connections Sensor Gas On R 1 2 3 R 3 2 1 Power Supply 12 24 V Linear Output 4 20 mA ...

Страница 6: ... technician and or the Distributor of BEINAT S r l should be contacted directly The installation of the SG500 probe its ordinary and extraordinary maintenance and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel The general test should be performed by issuing gas from a pre calibrated aerosol Acco...

Страница 7: ...consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following sympt...

Страница 8: ...all be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable...

Отзывы: