Connection Scheme 

normally

 close 

valve 230VAC

Electrical connections

Connection Scheme of the Detector

ATTENTION ! The relays are voltage free

WARNING.
Before connecting to the mains power, ensure the voltage is correct.
Carefully follow the instructions and the connections according to Regulations in force, keeping in mind
that the signal cables should be laid separate from the power cables.
An automatic cut-off switch (appropriately identified as devicesectioning  of the detector) should  be
incorporated in the electrical system, adequatelylocated and easily accessible.

N

Power  Supply

230  V

AC

Ph

1    2    3    4    5    6     7   8

N C

C

NO

N C

C

NO

Relay Alarme
Gas CO

Relay Alarm
Gas methane

N

Ph

1    2    3    4    5    6     7   8

N C

C

NO

N C

C

NO

Fan

  solenoid  valve  NC

Power  Supply

230  V

AC

Содержание CHCO

Страница 1: ...Installation EN 60079 29 2 The CHCO Detector has been designed and built according to European regulations to detect the presence of toxic and explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features this detector is suitable for household applications IThe CHCO Detector can detect the presence of two...

Страница 2: ...on 10A 250V resistive Insulation Class II Explosive Gas Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Toxic Gas CO toxic gas sensor Electrochemical Cell CO detector alarm sensitivity 30 300ppm CO gas detector alarm threshold according to norm EN 50291 on gas accumulation ALARMS 30 ppm within 120 minutes 50 ppm within 60 minutes 100 ppm within 10 minutes 300 ppm within 3 m...

Страница 3: ... concentration level has reached the 300ppm concentration or when the accumulation level is reached The relay contact is closed and an impulsive sound is issued 4 Explosive GAS ALARM indication LED This LED will light up and blink when the gas concentration level has reached 10 of LEL The relay contact is closed and an intermittent sound is issued 5 Electrochemical Cell sensor for Carbon Monoxide ...

Страница 4: ...cording to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO Relay Alarme Gas CO Relay Alarm Gas methane N ...

Страница 5: ...etectors with a normally close valve 230VAC Electricalconnections 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO solenoid valve NA Fan ...

Страница 6: ...the state of work Ceased the alarm the Led turns off it stops the sound of the buzzer and the connected devices will be disabled Test run with GAS a To test the explosive gas emit the gas from a pre calibrated bottle within 20 of the LEL inside the sensor concerned see item 6 of page 3 N B This test is recommended to be performed once a year Nota Do a test with a common cigarette lighter could dam...

Страница 7: ...the CHCO detection capsule status They may faulty or to have exhausted after 5 6 years must be replaced If the detector is repeatedly issuing an alarm 1 Check that there are no gas leaks 2 Check that there is not a persistent low concentration of CO Check see table on page 4 Make sure that together with the alarm it does not turn on even the FAULT led in this case proceed to the control of the sen...

Страница 8: ...cluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collecti...