Belonging to
Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.
Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and keep
it for future reference. It is also recommended to perform the electrical connections correctly as per enclosed
drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side
Channel: Beinat gas solutions
Electric connections also available on
CONFORMITY
Installation
and user guide
INSTALL IN SAFE
AREA, NO
ATEX
EN 50194
EN 45544-1-3
EN 50270
EN 61010-1
Compliant EN 60079-29-1
Installation EN 60079-29-2
Reports issued by TUV Italia
Control Unit from 1 to 2 Conventional sensors BX280
Rev. 10
Through the connection of 2 remote sensors, the BX280 control unit has been designed and built according to European
regulations to detect the presence of
toxic and/or explosive gas flexibly.
A microprocessor is used to create a complete surveillance and control system with maximum flexibility. Thanks to this
and its other features, the BX280 is suitable for civil and industrial applications.
The BX280 control unit has two danger levels:
1
st
LEVEL, 1
st
Pre-Alarm. This was set at 13 % of L.E.L. for all sensors.
2
nd
LEVEL, Main Alarm. This was set at 20% of L.E.L.
Other technical features make this control unit extremely versatile and reliable; for example, by using a series of micro-
switches it is possible to:
Select or disable the probe when not installed or faulty;
Select the type of gas to be detected (toxic or explosive);
Choose the relay functioning mode (pulsed or continuous);
Choose the main alarm relay shut-down time.
A TEST button checks the efficiency of both the unit and connected probe to ensure total control of the BX280.
Thanks to the Omega-type format both small and large systems can be built by exploiting the modularity of the DIN
rail in the previously set electrical panels.
In addition to the alarm signal light, it is fitted with an internal buzzer.