background image

 

“精锐”压缩冷凝机组 

“SLIM POWER”CONDENSING UNIT 

 

 

   

   

   

冷(无

  

锡)有

   

   

   

 

Beijer Ref (Wuxi) Co. Ltd 

PN: 

YAL0002-60 

Issue: 

Date:      01/01/20 
Page:       12 of 26  
EN: 

 

 

 

 

12 

 

HFC

(如

R404A

)制冷剂时,仅可使用

POE

油,在使用此类制冷剂时切莫混合其它的润滑油。当

POE

用于

HCFC

(如

R22

)制冷剂时也许可以混合少量其它润滑油。

 

Use only POE oil with HFC refrigerants. Do NOT mix POE oil with other oils when using HFC 
refrigerants (eg R404A). Small quantities of other oil types may be mixed with POE oil when 
using HCFC refrigerants (eg R22).

 

2.1.10 

机组的维护

Unit maintenance

 

冷凝器

Condenser

 

冷凝器建议每三个月进行一次清洁。

 

The condenser is recommended every three months to be clean.

 

系统运行

System Running

 

每六个月应进行系统检查,包括制冷剂充注量检查及电气连接检查。

 

System is recommended to be checked every six months, including refrigerant charge 

inspection and electrical connection check. 

 

2.1.11 

曲轴箱加热器

Compressor Crankcase heater

 

曲轴箱加热器将曲轴箱维持在一个适合的温度,能防止制冷剂发生迁移。曲轴箱加热器的效率是通过测量

油温来检查的,油温应该比环境温度高至少 10K。理想的油温应控制在

50℃~70℃

之间。在各种环境温度下,应

经常检查保证有适当的油温。

 

Crankcase  heater  maintain  the  crankcase  in  a  suitable  temperature,  prevent  the  occurrence  of 

refrigerant  migration.  The  efficiency  of  the  crankcase  heater  is  checked  by  measuring  the  oil 
temperature.   Oil  temperature should be higher than the  ambient  temperature for at least  10K. The 
expected  temperature  would  be  between 

50

~70

.  Recommend  to  check  oil  temperature  regular, 

for ensure that oil is in appropriate temperature.

 

2.1.12 

机组接线

Unit Electrical Connection

 

请参阅(电气图),图为壁挂室外型机组的推荐接线方式。图中机组的接线方式已完全反映出来,而其它

连接和总的系统连接则需安装者自行设计。 

Attached Wiring Schematic is recommended to electrical connection spacing (For detail, Please 

Refer  to  Wiring  Schematic).  If  other  connections  are  required  for  the  installation  of  the  system, 
please connect contractor or dealer

.

 

 

2.1.13 

旋锁阀

,

直线阀和压力软管

Roto-Lock Valve 

 Line Valve & Pressure hose

 

       旋锁阀注意事项

Roto-Lock Valve Attention

 

                    

在旋转机组中相应的旋锁阀的阀杆以前

,

压紧螺母必须先松开

,

以确保密封圈不会因为阀杆的转动而受到损坏

             

在旋转阀杆以后

,

用扭矩扳手以

13

扭矩将压紧螺母锁紧

,

防止制冷剂泄漏。具体数据如下:

 

 

Before turning valve rod of R/L valve, the gland nut must be released. Make sure that the 

sealing ring is not damaged by  the rotation of the valve rod. After turning valve rod, lock the gland 
nut with a torque wrench for 13 torque, to prevent leakage of refrigerant. The detail is below

 

                   

机组型号

Unit Model

 

压紧螺母

扭矩

Gland Nut

 

Torque

 

(N.m) 

旋转螺母扭矩

Rotary Nut 

Torque

 (N.m) 

压缩机排气端

Disc. Valve

 

压缩机吸气端

Suction Valve

 

BD020MZ2*D 

BDX020LZ2*D-AG 

BDN020LZ2*D-F 

BDN020LZ2*D 

13 

70-80 

100-110 

Содержание SLIM POWER

Страница 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Страница 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Страница 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Страница 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Страница 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Страница 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Страница 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Страница 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Страница 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Страница 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Страница 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Страница 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Страница 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Страница 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Страница 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Страница 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Страница 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Страница 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Страница 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Страница 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Страница 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Страница 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Страница 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Страница 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Страница 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Страница 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...