GN-9289 User Manual
Page 16 of (70)
G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx
4.4 How to supply the power correctly
- Refer the pin map of power RTB before wiring.
- Current capacity margin should be considered when you supply the power.
- Supply voltage 24Vdc which is recommended voltage level.
-
System and Field power must be supplied separately as the picture above.
※
If the power is supplied to each System and Field power from same power source, it would be vulnerable
to power noise.