OPT-2-EXTIO-BFI, Extended I/O for BFI-P2/H3 

 

 

By 

Date 

 

Revision 

Revision date 

 

Page 

JSG 

2020-06-23 

 

 

2 (2) 

 

OPTION MODULE CONTROL TERMINALS 

Pin 

Function 

     

 

 

Extended Digital Input 1 (DI6) 

Extended Digital Input 2 (DI7) 

Extended Digital Input 3 (DI8) 

NC 

Extended Relay Common 

Extended Relay Normally Open 
Contact 

Functional settings Relay Output

 

The additional relay output is fixed defined as “Drive Healthy”.  
If DOL Cascade function is activated by P8-14=1 then this output relay is to control DOL 
Pump2. 
With setting of P9-41=1 the relay is controlled by the internal PLC of BFI-P2 and BFI-H3 by the 
variable User Relay/Digital Output3. 
 

Functional settings Digital inputs  

The 3 digital inputs can be assigned to any function in Parameter Group 9 by first set of P1-
13=0. 
The inputs are named as Digital Input 6, Digital Input 7 and Digital Input 8. 

MECHANICAL INSTALLATION  

1) Option Module inserted into BFI Option Module Port  
2) DO NOT use undue force in inserting the option module into the options port.  
3) Ensure the option module is fitted securely before powering on the BFI.  
4) Remove terminal block header from option module prior to tightening connections. 
 Replace when wiring is completed. Tighten to Torque setting provided in Specifications. 

 

 

 Option Module Slot           

                                                            

         

   

 Option Module                                                                    

                                                                                                   

 

 

 

 

 

  

LED STATUS INDICATION  

The Extended I/O module has a Status LED – LED A (Green).  
LED A: Constant Green Indication - Modular is OK  
LED A: Flashing Green Indication – No Communication with drive  
LED A: LED Off Indication – No power to module 
LED B is not used.  

 

 