Additional Installation Tips

6.3 To Achieve Better EMC Protection

Use shielded cables for RS232 communication.

Use twisted pair and shielded cabling for RS422 and RS485.

Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.

Install and connect according to applicable specifications for the relevant bus
standard.

Use shielded cabling for Ethernet, preferably with foil and a braided shield.

D-sub covers should be shielded, and the shield should be connected to the
cover 360° where the cable enters.

Connect the shield at both ends.

Shielded cable

Not same potential

Ground plane 1

Ground plane 2

Ground plate

Ground plate
in another building

0.1 uF/250 V

5352

With longer distances, there is a risk that the ground potential may be different.
In that case, the shield should only be connected at one end. A good alternative
is to connect the other end of the shield to the ground via a 0.1

µ

F/250 V plastic

capacitor. Both ends are then connected to the ground in terms of HF, but only
connected to the ground at one end in terms of LF, thus avoiding the 50 Hz
grounding loops.

Metal cabinet

Metal cabinet

Terminal or connector

Terminal or connector

EMC cable gland

Plastic cable gland

Shielded cable

Shielded cable

Short distance

Cable clamp
in steel

5353

1. Use an EMC cable gland or regular plastic cable gland, remove the outer jacket

and connect the shield to the installation plate with a 360 ° metal cable clamp.

2. Place the 24 V DC and communications cabling in one cable trunk/cable duct

and 230/380 V AC in another. If the cables need to be crossed, cross them at
90 ° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.

Ferrite cores that are snapped onto the shielded cabling may remove minor
disturbances. Large ferrite pieces that are snapped onto unshielded cabling and
where the wires go 2-4 times around the cores are approximately 5-25 times more
efficient.

Beijer Electronics, MAEN852B

20

Содержание 06861B

Страница 1: ...EXTER K20m Installation Manual English MAEN852B 2014 10...

Страница 2: ...updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipment...

Страница 3: ...calData 11 4 ChemicalResistance 12 4 1 MetalCasing 12 4 2 Screen and Overlay Material 12 4 2 1 Autotex F157 207 12 4 2 2 Screen Surface 13 4 2 3 Screen and Keyboard Protector 14 5 Operator Panel Drawi...

Страница 4: ...sa powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserve...

Страница 5: ...duct contains a rechargeable battery this must only be changed in an area known to be non hazardous Replace the battery with aMS614S battery Use of anothertype ofbattery maypresent a risk of re orexpl...

Страница 6: ...roduct to the poweroutlet Peripheral equipment must be appropriate forthe application and location 1 4 During Use Keep the operatorpanel clean Emergency stopand othersafety functions may notbe control...

Страница 7: ...inch 155 mm 6 10 inch 100 mm 4 0 inch 46 4 mm 1 83 inch Caution The openings on the enclosure are for airconvection Do not cover these openings 2 2 Installation Process 1 Unpackand check the delivery...

Страница 8: ...ated draw along the outer sides ofthe holesandcutaccording to the markings For text strip 9 0 mm 13 0 mm 0 51 inch 0 35 inch 3 Secure the operator panel in position usingallthe fasteningholesand the p...

Страница 9: ...herwise errors in communication may occur Ensure that the voltage and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables ar...

Страница 10: ...to the Controller For information aboutthe cables to be used when connecting the operator panelto the controller please refer to the help le for the driverin question 2 2 3 Other Connections and Perip...

Страница 11: ...Real time clock battery rechargeable MS614S UL and cUL SII Micro Parts Ltd Power consumption at rated voltage Normal 0 1 A Maximum 0 3 A Display FSTN LCD 240 x64 pixels monochrome transmissive negativ...

Страница 12: ...3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded itis recommended to first test the c...

Страница 13: ...ffin oil Windex1 Cyclohexanol Persil powderin solution1 Wisk Diacetone alcohol Petroleum spirit1 1 Extremely faintglossingof the texture was noted Autotex withstands DIN 42 115 Part2 exposure of up to...

Страница 14: ...d Protector For harsh environments and exposure tooutdoorconditions it isrecommended to use a protective lm toguardthe screen and the keyboard from damage These optional parts canbe ordered from Beije...

Страница 15: ...Operator PanelDrawings 5 Operator Panel Drawings 5 1 Communication Ports RS 232 RS 422 RS 422 485 RS 485 Beijer Electronics MAEN852B 15...

Страница 16: ...Operator PanelDrawings 5 2 EXTER K20m Outline Beijer Electronics MAEN852B 16...

Страница 17: ...Operator PanelDrawings 5 3 EXTER K20m Text Strip 9 0 unit mm R1 4x Text max 15 5x7 5 Text max 18 5x7 5 4 5 11 25 19 0 138 0 20 5 20 5 20 5 19 0 Beijer Electronics MAEN852B 17...

Страница 18: ...aid between the panel s chassis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 T...

Страница 19: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur U...

Страница 20: ...e shield to the ground via a 0 1 F 250 Vplastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 Hz groun...

Страница 21: ...a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Installinga fan inside the cabinetwill even out the...

Страница 22: ...LVaccording to EN 60950 protection against electric shock andUL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay cont...

Страница 23: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial ris...

Страница 24: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120...

Страница 25: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: