background image

14

INV 2500 SERIES MANUAL REV 1 1/13

SECTION 3
OPERATION

3.3

OPERATIONAL CONSIDERATIONS

POWERING REACTIVE LOADS

 ( continued )

Several methods can be used to prevent tripping the protection circuits in the power source . One
common method is to insert a limiting impedance in series with the load. This could be in the form of
a fixed resistor or NTC (negative temperature coefficient) thermistor. Also, zero crossing switching can
be employed. Most commercial DC power supplies present a capacitive in-rush characteristic. Line
filters with large shunt capacitance may also cause considerable in rush current “spikes”. If not
accounted for these loads can trip protective circuits in the inverter. 

POWERING  LAMPS

  

 Tungsten filaments lamps, when cold, present a very low resistance. Once they are energized, their
resistance quickly climbs to it’s steady state value. This characteristic must be accounted for when
driving tungsten filament lamps. Like incandescent lamps, certain  Ni-Chrome based heaters will
present a 2:1 or 3:1 in rush when cold. The same methods for limiting in rush current for reactive loads
can be applied to tungsten or Ni-Chrome base elements.

POWERING MOTORS

 Driving an AC motor presents a special problem. Most motors require a starting current that can be
several times higher than the running current. This current may last for a few cycles to several seconds
depending on the construction and mechanical load on the motor. This current is sometimes referred
to as the motor’s “locked rotor” current. This current is not to be confused with the in- rush current that
usually occurs over the course of one or two cycles of the AC waveform.

The model 2500's fold back current limiting can be an advantage when starting motors. During the
starting period the motor will attempt to draw excessive power from the inverter. The fold back circuit
will reduce the output voltage in order to maintain the maximum output current. During this time the
current supplied to the motor will remain sinusoidal, this allows the motor to start rotating. Once the
motor reaches it’s normal operating speed, it generates the required “back EMF” to reduce  the supply
current to the nominal “run” value for the motor.

POWERING NON-LINEAR LOADS

 Loads utilizing rectifiers and SCRs  interact with the AC power source and have a significant effect
on the distortion of the output waveform. Consider the use of a bridge rectifier followed by a capacitive
filter, the current waveform associated with this circuit is illustrated below in figure 3-3. The input
current to this type of circuit is drawn in large “gulps” whenever the voltage across the capacitor falls
below the peak of the input waveform. The capacitor charging current is limited only by the series
impedance present in the wiring and capacitor .Because the impedance of large electrolytic capacitors
is very small this action causes a current wave form with a peak value several times the RMS value.
This ratio of peak current to RMS current is known as “ Crest Factor”. High values of crest factor  cause
distortion of the AC voltage waveform. 

 

The amount of distortion incurred is dependant on many factors and is beyond the scope of this
manual. It should be noted that this type of load may cause the output waveform to exhibit “flat topping”
This should not be associated with a defect of the inverter. Most “real world” electric distribution
systems exhibit this distortion for this reason.

Содержание INV 2500

Страница 1: ... ASSISTANCE CONTACT BEHLMAN CUSTOMER SERVICE DEPARTMENT PHONE TOLL FREE 1 800 874 6727 OR WRITE BEHLMAN CUSTOMER SERVICE DEPARTMENT 80 CABOT COURT HAUPPAUGE NY 11788 PHONE 631 435 0435 FAX 631 951 4341 FOR SALES INFORMATION PHONE 631 435 0435 USA 800 874 6727 FAX 631 951 4341 DATE 01 13 REV 1 ...

Страница 2: ...ipment in the presence of flammable gases or fumes Operation of any electrical instrument in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not remove equipment covers Component replacement and internal adjustments must be made by qualified maintenance personnel Do not replace components with power applied Under certain conditions dan...

Страница 3: ...the customer being liable for all shipping handling and repair costs When packing for reshipment use the original shock absorbent material and shipping container to preclude damage to the equipment Insure that the return authorization numbers RMA is available on the container for identification SHIPPING INSTRUCTIONS RACK MOUNTED UNITS 1 Box es must be double wall with minimum 350 lbs bursting test...

Страница 4: ...tion RMA number This number must be attached to the equipment sent back for warranty repair Equipment must be shipped back to Behlman prepaid No collect shipments will be accepted Behlman shall be excused from supplying warranty service if the unit s case has been open or if the unit has been subject to unauthorized repair All service outside the scope of this warranty shall be paid for by the Pur...

Страница 5: ...nal Alarm Contacts 2 4 Optional Step up Transformer 3 0 OPERATING INSTRUCTIONS 3 1 Controls and Indicators 3 2 Optional alarm contacts 3 3 Operational Considerations Load Limitations Powering Reactive Loads Powering Lamps Powering Motors Powering Non Linear Loads 4 0 TROUBLESHOOTING 4 1 Theory of Operation 4 2 Trouble Shooting 4 3 Maintenance 5 0 MECHANICAL OUTLINE ...

Страница 6: ...st The second option A1 will favor the AC line input and will switch to the inverter if the line is lost These features allow the unit to be incorporated into a user defined back up power system 1 1 SPECIFICATIONS INPUTS MODEL DC INPUT DC BURDEN full load DC BURDEN no load 2500 125 125 DC 20 31 AMPS 100 VDC 550 mA 20 2500 48 48 VDC 20 80 AMPS DC 38 VDC 1 7 A 20 AC INPUT optional bypass mode only 1...

Страница 7: ...2 inches on the sides Enclosures must be vented When rack mounting DO NOT mount the inverter by the mounting ears only If the unit is intended for use in a mobile or other high vibration application the use of additional support for the rear of the chassis is mandatory 2 2 WIRING Wiring to the inverter will vary depending on input voltage and any options ordered In addition local electrical codes ...

Страница 8: ...ny options The units have two a screw type terminal block located on the rear panel Compatible loads may be connected into this terminal block See section three of this manual for more information CAUTION FAILURE TO OBSERVE DC POLARITY ON THE INPUT TO THIS DEVICE MAY CAUSE DAMAGE TO INTERNAL CIRCUITRY THIS WILL VOID EQUIPMENT WARRANTY FIGURE 2 1 ...

Страница 9: ...quirements The output of the inverter is isolated from the DC input and the line This allows the output to be floating if required by end user s application Maximum continuous common mode potential is limited to 250Vac or 360Vdc Figure 2 2 illustrates a typical bypass configuration Figure 2 2 The recommended wire size for each model is listed below in table 2 1 These sizes are based on a maximum w...

Страница 10: ...g of the alarm functions are 0 3 amp 125 Vac maximum The figure 2 3 below illustrates the alarm internal wiring Figure 2 3 To prevent possible EMI electro magnetic interference alarm wiring should be accomplished with twisted pairs Shielding is also recommended This will prevent interference from entering or leaving the unit All alarm connections should be made with 6 inside diameter ring lugs A r...

Страница 11: ...iagram of the optional transformer configurations is provided in figure 2 4 Special units may vary and will be identified by a four digit engineering code Interconnecting wiring should be rated at 250Vac or better Ring lugs are recommended for all connections Figure 2 4 External Step up transformer block diagrams ...

Страница 12: ...nits provide screw type terminal blocks 6 AC LINE INPUT TERMINALS Screw type terminal block provided with alarm bypass option For connection to bypass source 7 FAN EXHAUST Heated air exhaust Minimum 4 inch clearance required for full power operation 8 DC INPUT Screw type terminal block to connect DC input 9 ALARM SIGNAL TERMINAL Screw type terminal block to connect alarm signals The table above li...

Страница 13: ...12 INV 2500 SERIES MANUAL REV 1 1 13 SECTION 3 OPERATION 3 1 CONTROLS AND INDICATORS FIGURE 3 1 FIGURE 3 2 ...

Страница 14: ...ted to the output terminals The DI bypass function can be verified by removing the DC input leave front panel breaker on Confirm that the DC IN and INVERTER LEDs turn off and the corresponding rear panel alarm contacts change state The AC IN LED will remain on and the AC IN contacts do not change state Use a voltmeter to confirm that the input AC is routed to the unit s output terminals or outlets...

Страница 15: ...ne or two cycles of the AC waveform The model 2500 s fold back current limiting can be an advantage when starting motors During the starting period the motor will attempt to draw excessive power from the inverter The fold back circuit will reduce the output voltage in order to maintain the maximum output current During this time the current supplied to the motor will remain sinusoidal this allows ...

Страница 16: ...n this case the load current is said to be discontinuous as it does not flow over the full cycle of the output waveforms This action can cause perturbations on the output waveform This may show up as ringing or clipping Ringing can be reduced by adding a small resistive pre load of about 10 to 20 watts across the output terminals FIGURE 3 3 ...

Страница 17: ... the sine wave information The result is a 400V p p pulse train at the output that contains the original sine wave information The 20 KHz carrier frequency is removed by a low pass LC filter This provides an amplified version of the original modulation signal to the output terminals The control circuitry on the output inverter assembly also provides output regulation and protective functions The o...

Страница 18: ...nverter Check polarity if ok the unit may have an internal fault Return for service WARNING Service of this device requires specialized equipment and trained personnel There are no internal user serviceable parts Removing the cover will expose individuals to hazardous voltages Refer service to qualified persons only 4 3 MAINTENANCE The INV 2500 series requires very little in the way of routine mai...

Страница 19: ...18 INV 2500 SERIES MANUAL REV 1 1 13 5 0 MECHANICAL OUTLINE ...

Отзывы: