TROUBLESHOOTING
LAMP DOES NOT COME ON AT ALL
Pilot Light is out before test...
1. Check AC supply - be sure unit has 24 hour AC supply (unswitched).
2. AC supply is OK, and indicator light is out, replace PC Board Assembly.
Pilot Light is on before test
3. Either the output is shorted or overloaded, or the battery is not connected.
4. Battery is severely discharged. Allow 48 hours for recharge and then retest. NOTE: This could be the result of a
switched AC supply to the unit (which has been turned off at some point), a battery with a shorted cell, an old
battery or a battery which has been discharged due to a long power outage and is not yet fully recharged.
LAMP COMES ON DIM WHEN TEST BUTTON IS PRESSED
1. Battery discharged - permit unit to charge for 48 hours and then retest. If lamps are still dim, check charger for
proper function. If charger functions correctly, replace battery.
LAMP COMES ON DIM WHEN AC POWER IS ON -
1. Check supply voltage and AC connections. This emergency light is provided with brownout protection. The AC
supply must be at least 80% of nominal (96V on a 120V line) for equipment to function normally. At lower voltages the
lamp will begin to glow dimly until the source voltage drops below the full “turn-on” point. NOTE: This condition may also
be caused by incorrectly connecting the voltage supply line to the wrong voltage transformer lead.
SAVE THESE INSTRUCTIONS
Figure 6
Back box
Securing Strap
Recess Trim Plate
Tempesta
+
-
ASSEMBLY
TEST
DIAGNOSTIC
WHITE - Neutral / Common
GREEN - Ground
BATTERY
NEG
POS
BATTERY -
CHARGER PC BOARD
LAMP
AUTOTEST DUAL INPUT VERSION
RED - 347V Line / Hot
TEMPESTA CHARGER BOARD
BLACK - 120V Line / Hot
ORANGE 277V Line / Hot
Figure 10
Figure 8
Figure 9
Screws & washers
not supplied
Waterproof
cap
926000294
Beghelli U.S.A., 3250 Corporate Way, Miramar, Florida, Tel: (800) 726-4316 Tel: (954) 442-6600 Fax: (954) 442-6677
08/08/2018
NOTE
:
Pink & Yellow
:
Connected Emergency ON; Not connected Emergency OFF
Violet & Yellow
:
Connected Self-Diagnostic OFF; Not connected Self-Diagnostic ON