MAINTENANCE 

1.  The equipment is to be repaired whenever the equipment fails to operate as intended during the duration test.  

Written records of test results and any repairs made must be maintained. Beluce Canada Inc. strongly recommends 
compliance with all Code requirements.

2.  The lamps listed herein when used according to the instructions with this unit are in accordance with the 

requirements of CSA Standard C22.2, No. 141 – Unit Equipment for Emergency Lighting.

3.  Clean exit face(s) on a regular basis.
NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement
 

     parts not furnished by Beluce Canada Inc., may cause equipment failure and will void the warranty.

TROUBLESHOOTING 

LEDS DO NOT COME ON AT ALL
1.  Check AC supply be sure unit has 24 hour AC supply (unswitched).
 

The AC supply must be at least 80% of nominal (96V on a 120V line) for equipment to function normally.

 

At lower voltages the LED lamps will begin to glow dimly until the source voltage drops below the full “turn on” point.

 

NOTE: This condition may also be caused by incorrectly connecting an AC Volt supply line to the lead.

2.  Check all AC connections
3.  AC supply is OK, replace LED Board Assembly.

SAVE THESE INSTRUCTIONS

Chassis GND

LED Board

AC ONLY SIGN

Chassis GND

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

LED Board

AC & UNIVERSAL DC SIGN

YELLOW Positive 6 to 24VDC

PURPLE Negative

Emergency Supply

FROM Battery Pack

SELF-POWERED SIGN

Chassis GND

24 hours

Unswitched Supply

GREEN Ground

BLACK 105 to 360VAC

WHITE Neutral

LED Board

DUAL UNIVERSAL AC SIGN

From Generator OR

Emergency Supply

BROWN 105 to 360VAC

BLUE Neutral

NOTE: Cap unused AC Wire!

NOTE: Cap unused AC Wire!

24 hours

Unswitched Supply

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Chassis GND

LED Board

NOTE: Cap unused AC Wire!

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Ni-Cd

Battery

Ceiling/End Mount

Wall Mount

926000122 

Figure 1

Figure 3

Figure 2

Beluce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673