MAINTENANCE
CAUTION:
Always turn off AC power before servicing. The servicing of any parts, should be performed by qualified
service personnel. The use of replacement parts not furnished by BeLuce Canada Inc. may cause
equipment failure and will void the warranty.
TROUBLESHOOTING
EXIT SIGN DOES NOT COME ON AT ALL
1. Check AC supply and all AC connections - be sure exit has 24 hour AC supply (unswitched).
2. Check supply voltage and AC connections. The AC supply must be at least 80% of nominal (96V on a 120V line)
for equipment to function normally. At lower voltages the LEDs may begin to glow dimly until the source voltage
drops below the full “turn-on/off” point.
NOTE: This condition may also be caused by incorrectly connecting a 120 Volt supply line to the 347 Volt lead.
3. AC supply is OK; replace LED circuit board assembly.
SAVE THESE INSTRUCTIONS
Chassis GND
LED Board
AC ONLY SIGN
Chassis GND
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
LED Board
AC & UNIVERSAL DC SIGN
YELLOW Positive 6 to 24VDC
PURPLE Negative
Emergency Supply
FROM Battery Pack
SELF-POWERED SIGN
Chassis GND
24 hours
Unswitched Supply
GREEN Ground
BLACK 105 to 360VAC
WHITE Neutral
LED Board
DUAL UNIVERSAL AC SIGN
From Generator OR
Emergency Supply
BROWN 105 to 360VAC
BLUE Neutral
NOTE: Cap unused AC Wire!
NOTE: Cap unused AC Wire!
24 hours
Unswitched Supply
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Chassis GND
LED Board
NOTE: Cap unused AC Wire!
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Ni-Cd
Battery
Figure 3
Figure 1
Figure 2