TROUBLESHOOTING
IMPORTANT NOTE: If the Time Delay optional feature is installed, emergency lamps will remain lit for up to
10 minutes following the resumption of regular/mains AC power to the unit.
EMERGENCY LAMPS DO NOT COME ON AT ALL
“AC ON” LED indicator is off before test...
1. Check AC supply - be sure unit has 24 hour AC supply (unswitched).
2. AC supply is OK, and indicator light is out, replace PC Board Assembly.
“AC ON” LED indicator is on before test...
1. Either the output is shorted or overloaded, or the battery is not connected.
2. Battery is severely discharged. Allow 24 hours for recharge and then retest. NOTE: This could be the result of a
switched AC supply to the unit (which has been turned off at some point), a battery with a shorted cell, an old
battery or a battery which has been discharged due to a long power outage and is not yet fully recharged.
EMERGENCY LAMPS COME ON DIM WHEN TEST SWITCH IS ACTIVATED
1 . Battery discharged - permit unit to charge for 24 hours and then retest. If lamps are still dim, check charger for
proper function. If charger functions correctly, replace battery.
EMERGENCY LAMPS COME ON WHEN BATTERY IS FIRST CONNECTED
1 . Battery may be connected in reverse polarity. Check connections. Connect Positive lead to Positive battery terminal
and Negative lead to Negative battery terminal. The lamps should then turn off and the charge indicator should light
when AC power is applied.
EMERGENCY LAMPS COME ON DIM WHEN AC POWER IS ON -
1 . Check supply voltage and AC connections. This emergency light is provided with brownout protection. The AC
supply must be at least 80% of nominal (96V on a 120V line) for equipment to function normally. At lower voltages the
emergency lamps will begin to glow dimly until the source voltage drops below the full “turn-on” point. NOTE: This
condition may also be caused by incorrectly connecting a 120 Volt supply line to the wrong voltage transformer lead.
SAVE THESE INSTRUCTIONS
MAINTENANCE
1. Beluce Canada Inc.
strongly recommended compliance with all Code requirements.
2. Clean lenses on a regular basis.
NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement
parts not furnished by Beluce Canada Inc. may cause equipment failure and will void the warranty.
Figure 1
Figure 2
Figure 6
Figure 7
Figure 3
TEST
CHARGE
AC ON
WHITE - Neutral / Common
GREEN - Ground
BATTERY
NEG
-
POS
+
BATTERY -
LAMP +
LAMP
-
CHARGER PC BOARD
ASSEMBLY
LAMPS
STANDARD TRIPLE INPUT VERSION
RED - 347V Line / Hot
FUSE
CHARGER BOARD
BLACK - 120V Line / Hot
ORANGE - 277V Line / Hot
Figure 5
1 Battery Unit
(+)
( )
Black
Red
2 Battery Unit
(connected in series)
(+)
( )
Black
Red
(+)
( )
2 Battery Unit
(connected in parallel)
(+)
( )
Black
Red
(+)
( )
conduit bushing
wire leads
magnetic
test switch
lens
cover
tether
926000307
strap mounting hole
back of housing
Figure 4
gasket
Beluce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673
04/09/2019