TROUBLESHOOTING 

IMPORTANT NOTE:   If the Time Delay optional feature is installed, emergency lamps will remain lit for up to  
 

 

 

 

10 minutes following the resumption of regular/mains AC power to the unit.

EMERGENCY LAMPS DO NOT COME ON AT ALL
   “AC ON” LED indicator is off before test...
1.   Check AC supply - be sure unit has 24 hour AC supply (unswitched).
2.   AC supply is OK, and indicator light is out, replace PC Board Assembly.
   “AC ON” LED indicator is on before test... 
1.   Either the output is shorted or overloaded, or the battery is not connected.
2.   Battery is severely discharged. Allow 24 hours for recharge and then retest. NOTE: This could be the result of a
 

switched AC supply to the unit (which has been turned off at some point), a battery with a shorted cell, an old

 

battery or a battery which has been discharged due to a long power outage and is not yet fully recharged.

EMERGENCY LAMPS COME ON DIM WHEN TEST SWITCH IS ACTIVATED
1 .   Battery discharged - permit unit to charge for 24 hours and then retest. If lamps are still dim, check charger for
 

proper function. If charger functions correctly, replace battery.

EMERGENCY LAMPS COME ON WHEN BATTERY IS FIRST CONNECTED
1 .   Battery may be connected in reverse polarity. Check connections. Connect Positive lead to Positive battery terminal    
 

and Negative lead to Negative battery terminal. The lamps should then turn off and the charge indicator should light    

 

when AC power is applied.

EMERGENCY LAMPS COME ON DIM WHEN AC POWER IS ON -
1 .   Check supply voltage and AC connections. This emergency light is provided with brownout protection. The AC 
supply must be at least 80% of nominal (96V on a 120V line) for equipment to function normally. At lower voltages the 
emergency lamps will begin to glow dimly until the source voltage drops below the full “turn-on” point. NOTE: This 
condition may also be caused by incorrectly connecting a 120 Volt supply line to the wrong voltage transformer lead.

 

SAVE THESE INSTRUCTIONS

MAINTENANCE 

1.   Beluce Canada Inc.

 

strongly recommended compliance with all Code requirements.

2.   Clean lenses on a regular basis.
NOTE:  The servicing of any parts should be performed by qualified service personnel only. The use of replacement
 

 

parts not furnished by Beluce Canada Inc. may cause equipment failure and will void the warranty.

Figure 1

Figure 2

Figure 6

Figure 7

Figure 3

TEST

CHARGE

AC ON

WHITE - Neutral / Common

GREEN - Ground

BATTERY

NEG

-

POS

+

BATTERY -

LAMP +

LAMP 

-

CHARGER PC BOARD

ASSEMBLY

LAMPS

STANDARD TRIPLE INPUT VERSION 

RED - 347V Line / Hot

FUSE

CHARGER BOARD

BLACK - 120V Line / Hot

ORANGE - 277V Line / Hot

Figure 5

1 Battery Unit

(+)

(  )

Black

Red

2 Battery Unit

(connected in series)

(+)

(  )

Black

Red

(+)

(  )

2 Battery Unit

(connected in parallel)

(+)

(  )

Black

Red

(+)

(  )

conduit bushing

wire leads

magnetic 

test switch

lens

cover

tether

926000307

strap mounting hole

back of housing

Figure 4

gasket

Beluce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673