background image

LOGICA FM CONTROL UNIT BY BEGHELLI

code 21102

Control Unit for the centralised control of normal 

and emergency lighting systems

INSTALLATION

AND OPERATING INSTRUCTIONS

Содержание 21102

Страница 1: ...LOGICA FM CONTROL UNIT BY BEGHELLI code 21102 Control Unit for the centralised control of normal and emergency lighting systems INSTALLATION AND OPERATING INSTRUCTIONS ...

Страница 2: ...Date and Time Settings p 6 Searching for Logica FM Control Units Node searching p 7 Scheduling Functional and Autonomy Tests p 8 GROUPS p 10 Assigning a Luminaire to a Group p 10 MENU p 10 Luminaires Menu p 10 Maintenance Menu p 10 Manual Test p 10 Emergency p 11 Management Test p 12 Control Unit Management p 13 Date Time Changes p 13 Printing p 13 Language p 14 Outputs OUT1 OUT2 OUT3 on off p 14 ...

Страница 3: ...N networks Wi Fi interface for PC connection To control the system from a remote PC you need to get the Logica Visual software code 12139 or the SD Manager software code 20109 The Logica FM Control Unit performs the following tasks SYSTEM MONITORING The Logica FM Control Unit continuously monitors the luminaires connected to it and it detects and signals any malfunctions SYSTEM CONTROL The Logica ...

Страница 4: ...CODE 1213 DIN PRINTER CODE 3284 DTR YELLOW TX BLUE RX GREY GND BLACK USE AND TERMINATION OF RS 485 LINES The control unit is equipped with 2 independent RS 485 lines RS485_A and RS485_B both with adaptation of the line impedance by inserting 2 riders at 2 54 pitch Line adaptation is necessary when the control unit is located as a terminal element of BUS 485 start or end of the route To adapt the R...

Страница 5: ...he ESC Akey Other functions of the keys are listed below Use the DOWN Cand UP Dkeys to change a value for example in the Date and Time Settings menu with the hour indication 08 flashing press Dto increase the value to 09 press Cto decrease the value to 07 and press the OK B key to confirm the entered value by reference to the example given at the previous point if after changing the hours value to...

Страница 6: ...ter the menu that shows the date cur rently set on the Control Unit and the day indication will be flashing Press D until the day of interest is displayed then press B to confirm Now the month indication will start flashing To change it follow the same procedure as for setting the day Change date time 01 01 2005 00 00 Apply the same method to set the year hour and minu tes Press B to confirm the v...

Страница 7: ...ire the display will show NORMAL SEARCH which will then be replaced by the following indications 008 008 number of luminaires found total number of luminaires stored on the Control Unit Config in progress 008 008 When the total number of luminaires stored on the Control Unit reaches the number of luminaires installed in the system press A and this screen will appear showing how many luminaires hav...

Страница 8: ...correct operation of the system the following must be set Date and time of the next Functional Test Date and time of the next Autonomy Test Time interval between repeated Functional Tests Time interval between repeated Autonomy Tests Example of how to set the date and time for the next Functional Test Now press Bto show the date of the next Functional Test currently stored on the Control Unit To s...

Страница 9: ... not belong to the group 1 the luminaire belongs to the group Before the first configuration the row has sixteen 0 i e the luminaire F12345 does not belong to any group the cursor will flash on the last zero to the left that cor responds to group 1 Press B to move to the next group A to move to the previous group Dto include the luminaire in the group Cto exclude the luminaire from the group SA PS...

Страница 10: ...for about 30 seconds during which time the luminaire tube and battery efficiency is checked an Autonomy Test consists in turning on a luminaire over a longer time at the end of which the battery efficiency is checked Normally Functional and Autonomy Tests are run automatically at regular intervals according to the schedule set by the user see Scheduling Functional and Autonomy Tests but it is also...

Страница 11: ...re turns off it can be turned back on by enabling the state of emergency Enable the state of emergency the luminaire turns on Turn off the luminaire is turned off permanently it cannot be turned back on unless the lumi naire itself detects power being fed from the mains This feature can be useful to preserve battery power when for instance the power supply to the system needs to be cut off for a l...

Страница 12: ...tween repeated Functional Tests Time interval between repeated Autonomy Tests For further details on how to set test dates times and time intervals see section Scheduling Functional and Autonomy Tests Based on their unique identifying addresses LOGICA luminaires are divided into EVEN numbe red and ODD numbered luminaires Using the EVEN ODD TEST menu you can decide whether to perform an autonomy te...

Страница 13: ...d even numbered luminaires Errors For each faulty luminaire a warning is given that specifies the type of fault e g 8W neon tube error battery charging error etc Reports For this menu you must enter a start date and an end date for the report The prin tout will list significant actions that occurred over the set time frame involving the Logica Control Units by Beghelli installed in the system The ...

Страница 14: ...3 on off The user can enable or disable one or more outputs to signal errors in the system Outputs OUT1 OUT2 OUT3 Active Open Closed Once enabled outputs can be set in N C or N A mode N C means the output will open if an error occurs N A means the output will close if an error occurs k O c s E DC RELAY C C POWER SUPPLY 12 24 V ...

Страница 15: ...REATE RADIO NETWORK To go to menu search for luminaires in the system FIND NODES CONT delete all luminaires stored on the Control Unit DELETE NODES delete the communication network for tree structured luminaires DELETE RADIO NETWORK create a radio network between the Control Unit and all luminaires in the system CREATE RADIO NETWORK STATUS MENU This menu allows the user to access additional inform...

Страница 16: ...onnect the device from the mains Warning this product contains materials that may be harmful if disposed in the environment The device must not be disposed of as municipal waste It must be subjected to separate col lection to avoid environmental pollution In compliance with Directive 2002 96 and imple menting national laws on end of life product disposal a failure to comply with the above is sanct...

Отзывы: