B6031I Series Deep well Pump Inverter User Manual
15
Function
Code
Name
Setting
Range
Factory
Setting
Description
b00.01
Water-level of
Deep Well and
Upper Reservoir
Auto Controlling
Run Frequency
000.0~
060.00
50.00Hz
Water-level of deep well and upper reservoir
auto control run frequency value
b00.02
Pressure Setting
Value
0.0~100.0
bar
3.0bar
Set according to the actual requirements of user
b00.03
Phase Selection
0~1
1
Single phase or three phase motor selection
0: Three phase
1: Single phase
b00.04
Motor Rotating
Direction
0~1
0
0: Forward
1: Reverse
b00.05
Restart After
Power-on
0~1
1
0: Invalid
1: Valid
b00.06
Control Mode
0~6
5
0: The water-level of deep well and upper
reservoir auto controlling
5: The water-level of deep well auto controlling
and constant pressure water supply
b00.07
Maximum
Transducer
Setting Range
0.0~100.0
bar
16.0bar
E.g. If the rated max. range of transducer is 10
bar, b00.07 should be set to10.0
b00.08
High Water
Pressure Alarm
Value
0.0~100.0
bar
10.0bar
When the pressure is higher than this preset
value, the controller alarms, halts and displays
“HP”; when the pressure is lower than this
preset value, breakdown recover and running
b00.09
Low Water
Pressure Alarm
Value
0.0~100.0
bar
0.5bar
When the pressure is lower than this preset
value for a Low Pressure Running Time, the
controller alarms, halts and displays “LP”;
restart automatically from breakdown after 10
minutes’ downtime
b00.10
Low Pressure
Running Time
00~300s
20s
b00.11
Reserved
000.0~
100.0
000.0
Need to set as 0.000
b00.12
Reserved
0~30000
0
b00.13
Reserved
01~60
40
b00.14
Restore Defaults
0~2
0
0: No action
1: Set to default
2: Clear error records
b00.15
Password of
Group br08
0~65535
00000
Don’t try to enter or will cause abnormal
operation and damages.