2–5
Application - 2
NOMINAL VOLTAGE
________ volts
NOMINAL CURRENT
________ amps
V.T. CONFIGURATION
LINE-LINE line-ground
V.T. CONFIGURATION
line-gnd_to_line-line
SYNC-CHECK PHASE
A b c
PHASE ROTATION
a-c-b A-B-C
PULSE RELAY
o8 o7 o6 o5 o4 o3 o2 o1
RELAY SEAL-IN TIME OUT1
________ cycles
System Setup
The system setup consists of defining common
information such as CT and VT ratios, nominal voltage
and current ratings, VT configuration, phase rotation,
etc. These parameters should be entered before
proceeding to the configuration or setpoint and time
delay settings for particular functions. The values or
selections shown below are only examples. Record
and communicate the following information using the
Functional Configuration Record Form in Appendix
A.
The secondary VT voltage when primary voltage is
equal to the 1 per unit rating.
The secondary current of the phase CTs when the pri-
mary current is equal to the 1 per unit rating. Nominal
voltage and current are used in the per unit power cal-
culation.
Indicates the VT Configuration. When
LINE-GROUND
is selected, functions 27 and 59 may operate for
line-ground faults. If this is not desired, the
LINE-GND_TO_LINE-LINE
selection may be used.
When
LINE-GND TO LINE-LINE
is selected, the re-
lay internally calculates line-line voltages from
line-ground voltages for all voltage-sensitive func-
tions. This Line-Ground to Line-Line selection should
be used only for a VT nominal secondary voltage of
69 V (not for 120 V). For this selection, the nominal
voltage entered should be line-line nominal voltage,
which is
e
e
e
e
e
3 times line-ground nominal voltage. The
V2 connected VT must be configured line-ground if
VT CONFIGURATION from above is
LINE-
GROUND
. If VT configuration is
LINE-LINE
or
LINE-
GND_TO_LINE-LINE
, then V2 must be configured
line-line.
Indicates selected phase for sync check (25) function.
Phase Rotation.
Indicates outputs chosen for pulse operation. When
selected, output will remain energized for the time
delay specified in the
RELAY SEAL-IN TIME
(see
below), and then drop out. With pulse operation, the
selected relay will drop out after the delay, even if
the tripping function remains out of band.
Minimum time the output contact will remain picked
up to ensure proper seal-in, regardless of the sub-
sequent state of the initiating function. Individual Seal
-
In settings are available for all outputs.
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...