Programming
TX1200
53
Version: 1.1
rTotalVolume : LREAL;
nCoolingEnergy : DINT;
nHeatingEnergy : DINT;
bBusy:
this bit is set for as long as the function block is active.
bError:
the output becomes TRUE as soon as an error occurs. This error is described via the
iErrorId
variable.
iErrorId:
this output outputs an error code in the event of an error (see
).
bError
goes
TRUE at the same time.
strMP_Serial_Number:
structure for the serial number. (see
).
rSensor1Value:
sensor 1 value in mV/Ohm (0...65535).
rRelativeVolumetricFlow:
relative volume flow rate in % (0...100).
rAbsoluteVolumetricFlow:
absolute volume flow rate in l/s (0...100).
rGlycolConcentration:
glycol concentration in % (0...100).
rTemperature1_Remote:
temperature1 remote in °C (-20...12).
rTemperature2_Integrated:
temperature2 integrated in °C (-20...12).
rDeltaTemperature:
temperature delta in K (0...14).
rAbsoluteCoolingPower:
absolute cooling power in kW (0...21.5).
rAbsoluteHeatingPower:
absolute heating power in kW (0...21.5).
rTotalVolume:
total volume in m³ (0...214748.36).
nCoolingEnergy:
cooling energy in kWh (0...21474836).
nHeatingEnergy:
heating energy in kWh (0...21474836).
6.2.19
MP_UST_3
This function block is used to control and monitor a multi-I/O module UST3.
MP_Address
is used to specify the MP-Bus device with which the function block is to communicate.
bStart
activates communication with the MP-Bus device.
bBusy
indicates that the function block is active. If
bStart
remains TRUE, the device is addressed cyclically with a period specified by the time in
TMPolling
. The time
must be set greater than one second.
bError
indicates an error in communication with the actuator. The type
of the error can be read with
iErrorID
.