Commissioning
SCT5xxx
27
Version: 1.0
4.1
Mounting instructions, mounting options
• Make sure that the working environment is safe during assembly, maintenance and installation work.
Interrupt the power supply of the primary conductor and secure against being switched on again
inadvertently.
• Install the current transformer on the primary conductor.
• To do this, feed the primary conductor through the opening of the current transformer housing
• The device can be fastened directly to the primary conductor or alternatively to a mounting plate. Use
the fastening materials included in the scope of delivery for this.
Fig. 16: Mounting SCT5xxx
• Fastening the base plate with screws in the four holes
• Free suspension on the cable with the help of cable ties through the hooks on the back for attachment
• All current-carrying conductors/lines must be routed together through the
, see Fig, "Use in single-phase and 3- and 4-pin three-phase systems".
• An existing
must not be routed through the transformer
• Bending of the primary conductors may only take place from the specified minimum distance. The
bending radii specified by the manufacturers must be observed.
Fig. 17: Calculation bending primary conductor: *distance to 90° angle = 2x outer diameter
• The conductors are to be centered in the measuring transformer
Содержание SCT Series
Страница 2: ......
Страница 4: ...Table of contents SCT5xxx 4 Version 1 0...
Страница 25: ...Technical data SCT5xxx 25 Version 1 0 Fig 15 Side view front view all dimensions in mm...
Страница 28: ...Commissioning SCT5xxx 28 Version 1 0 Fig 18 Center conductors...
Страница 32: ...Commissioning SCT5xxx 32 Version 1 0 Fig 21 SCT5xxx block diagram...
Страница 40: ......