Technical data
SCT6xxx
35
Version: 1.3
3.4
SCT66xx | Split-core current transformers, size 6
3.4.1
SCT66xx | General
Primary side
SCT66xx-xxxx
Thermal rated continuous current I
cth
1,0 * I
N
Rated short-time thermal current I
th
60 * I
N
/1 s
Rated impulse current I
dyn
2,5 * I
th
Rated frequency f
R
50..60 Hz
Secondary side
SCT66xx-xxxx
Secondary rated current I
sr
5 A
Overcurrent limiting factor
FS5
Operating conditions
SCT66xx-xxxx
Permissible ambient temperature range during
operation
-5…+50 °C
Permissible ambient temperature range during
storage
-25 … +70 °C
Permissible relative humidi
5 … 85 %
Operating height
Up to 2000 m
Protection class
IP20
Insulation characteristics (only for insulated pri-
mary conductors)
SCT66xx-xxxx
Rated insulation level U
m
0,72/3/- kV
Insulation class
E
Gerneral data
SCT66xx-xxxx
Max. Diameter conductor bushing primary conductor 42,4 mm
Conductor cross section secondary
1,5 mm²
Stripping length
10 mm
Size
6
Dimensions (W x H x D)
67 mm x 96 mm x 69 mm
Weight
420 g
Standards and regulations
SCT66xx-xxxx
Approvals/Markings
CE
Standards/Regulations
EN 61869-1; EN 61869-2; IEC 61010-1