![Beckhoff PS9031-4820-0001 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/beckhoff/ps9031-4820-0001/ps9031-4820-0001_documentation_2719283015.webp)
Technical data, application notes, wiring
PS9031-4820-0001
15
1.0
4.3
Buffer storage time
The buffer time (sometimes also called autonomy time) is the maximum timespan over which the capacitor
can maintain the required output current. The buffer time mainly depends on the output current in buffer
operation.
Any number of buffer modules can be connected in parallel in order to increase the buffer time.
Buffer time
Min.
100 ms
At 45 V, 20 A
Min.
200 ms
At 45 V, 10 A
Typ.
150 ms
At 45 V, 20 A
Typ.
300 ms
At 45 V, 10 A
Typ.
21 s
At 45 V, 0.1 A
9: Buffer time, typ.