Technical data, mounting, wiring
PS1111-2403-0002
12
Version: 1.0
3.3
Input inrush current
An NTC limits the input inrush current after the input voltage is switched on. The inrush current surge
depends on the input voltage and the ambient temperature. The output load has no influence on the value of
the inrush current surge.
The charge current of the interference suppression capacitors during the first few microseconds after
switching on is not taken into account.
AC 100V
AC 120V
AC 230V
Input inrush
current
Typ. 14A
peak
18A
peak
40A
peak
At +40°C, cold start
Typ. 12A
peak
16A
peak
35A
peak
At +25°C, cold start
Max. 17A
peak
22A
peak
48A
peak
At +40°C, cold start
Max. 15A
peak
20A
peak
43A
peak
At +25°C, cold start
Inrush energy
Max. 0.3A
2
s
0.4A
2
s
1.7A
2
s
At +40°C, cold start
Fig. 3: Switch-on behavior at nominal load, typ., 230Vac@25°C; zoom inrush current surge
Fig. 4: Switch-on behavior at nominal load, typ., 120Vac@25°C; zoom inrush current surge