Technical data, mounting, wiring
PS1061-2405-0000
23
Version: 1.0
3.13
Environment
Environment
Operating temperature
1)
-10 °C to + 70 °C
Reduction of the output power according to
Fig.
Output current over ambient temperature
Storage temperature
-40 °C to + 85 °C
For storage and transport
Output load reduction
3W/°C
+55 °C to +70 °C
7.5 W/1000 m or 5 °C/1000 m
Above > 2000 m, see fig.
Output current to
installation altitude
The output load reduction is not hardware-controlled. Take this into account in
order to stay below the nominal current limits so that the device is not
overloaded.
Humidity
2)
5 % to 95 % r.h.
According to IEC 60068-2-30
Atmospheric pressure
110 kPa - 54 kPa
see fig.
Output current to installation altitude
Installation altitude
Up to 5000 m
Vibrations, sinusoidal
3)
2-17.8 Hz: ±1.6 mm;
17.8-500 Hz: 2 g 2 hours/axis
According to IEC 60068-2-6
Impacts
3)
30 g 6 ms, 20 g 11 ms
3 impacts/direction,
18 impacts in total
According to IEC 60068-2-27
Overvoltage category
II
According to IEC 60664-1 for altitudes up to
5000 m
Impulse voltages
4 kV (according to overvoltage
category III)
Input to PE
According to IEC 60664-1 for altitudes up to
2000 m
Degree of pollution
2
According to IEC 60664-1, non-conductive
Acoustic noise
The power supply unit can produce audible noise when idling, overloaded or
short circuited.
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2 cm below the device.
2)
Do not energize when condensation is present!
3)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15 mm and a thickness of
1.3 mm and standard installation position.
Fig. 10: Output current over ambient temperature; output current over installation altitude