Bit
Name
Description
default
R32.15 -
reserved
0
bin
...
...
...
...
R32.12 -
reserved
0
bin
R32.11 enTh2
0
bin
Threshold 2 not active
0
bin
1
bin
Threshold 2 active
R32.10 enTh1
0
bin
Threshold 1 not active
0
bin
1
bin
Threshold 1 active
R32.9
enOverProt
0
bin
Measuring range limitation not active
1
bin
1
bin
Overrange protection active
R32.8
-
reserved
0
bin
...
...
...
...
R32.5
-
reserved
0
bin
R32.4
enSiemensFormat 0
bin
Siemens output format not active
0
bin
1
bin
Siemens output format active
R32.3
enAverageFormat
0
bin
Signed amount representation not active
0
bin
1
bin
Signed amount representation active
R32.2
disWdTimer
0
bin
Watchdog timer is active (the watchdog is triggered if no
process data are received for 100 ms)
0
bin
1
bin
Watchdog timer is not active
R32.1
enManScal
0
bin
Manufacturer scaling is not active
1
bin
1
bin
Manufacturer scaling is active
R32.0
enUsrScal
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
R33: User scaling - offset
This register contains the offset of the user scaling. The user scaling can be activated in the feature register
through bit
R34: User scaling - gain
This register contains the gain of the user scaling. The user scaling can be activated in the feature register
through bit
8
+ 1, 1
dec
corresponds to 0x0100).
R35: Threshold 1
Threshold 1 is entered in register R35. The threshold can be activated in the feature register through bit
R36: Threshold 2
Threshold 2 is entered in register R36. The threshold can be activated in the feature register through bit
.11.