Product overview
KL4494
8
Version: 2.0.0
2.3
Diagnostic LEDs
The four green RUN LEDs indicated the operating state of the terminal channels.
Fig. 2: KL4494 - LEDs
Meaning of the LED displays
LED
Color
Channel
State
On
off
Run IN 1
green
Input 1
normal operation
A watchdog-timer overflow has
occurred. The green LEDs go
out if no process data are
transferred between the
controller and the Bus Coupler
for more than 100 ms.
Run IN 2
Input 2
Run OUT 1
Output 1
Run OUT 2
Output 2
2.4
Basic function principles
Analog input channels
The analog input channels of the KL4494 process signals in the range from -10 V to +10 V with 12-bit
resolution (4095 steps). The inputs are single-ended inputs with a common ground potential.
Format of the input values
In the delivery state the process data are shown in two's complement form ( -1
integer
corresponds to 0xFFFF).
can be selected via the feature register R32 as an alternative.
Measured value
Input data
decimal
hexadecimal
-10 V
-32768
0x8000
-5 V
-16383
0xC001
0 V
0
0x0000
+5 V
16383
0x3FFF
+10 V
32767
0x7FFF
Process data equations
The process data that are transferred to the Bus Coupler are calculated using the following equations:
Содержание KL4494