Access from the user program
KL4414, KL4418, KL4424, KL4428
40
Version: 3.0.0
• If you write values into the user registers and have previously entered the user code word (0x1235) in
the code word register, these values are stored in the RAM registers and in the SEEPROM registers
and are therefore retained if the terminal is restarted.
The code word is reset with each restart of the terminal.
Feature register (R32)
The feature register specifies the terminal's configuration. Default: 0x0006 (6
dec
)
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
-
-
-
-
-
-
-
enUserAct-
Value
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
-
-
enSignRepr
-
enSignAm-
Repr
enWdTimer
enManScal
enUsrScal
Key
Bit
Name
Description
default
R32.15
-
reserved
0
bin
...
...
...
...
R32.9
-
reserved
0
bin
R32.8
enUserActValue
0
bin
Manufacturer switch-on value active
0
bin
1
bin
User switch-on value active
R32.7
-
reserved
0
bin
R32.6
-
reserved
0
bin
R32.5
enSignRepr
0
bin
Signed representation is not active
0
bin
1
bin
Signed representation is active
R32.4
-
reserved
0
bin
R32.3
enSignAmRepr
0
bin
Two's complement representation is active
0
bin
1
bin
Signed amount representation is active (-1
dec
= 0x8001)
R32.2
enWdTimer
0
bin
Watchdog timer is not active
1
bin
1
bin
Watchdog timer is active (the watchdog is triggered if no
process data are received for 100 ms)
R32.1
enManScal
0
bin
Manufacturer scaling is active
1
bin
1
bin
Manufacturer scaling is not active
R32.0
enUsrScal
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
R33: user scaling - offset (B
w
)
This register contains the offset of the user scaling.
User scaling can be enabled in the feature register via bit
R34: user scaling - gain (A
w
)
This register contains the gain of the user scaling. Default: 0x0100 (256
dec
)
User scaling can be enabled in the feature register via bit
R35: user switch-on value
If the user switch-on value has been enabled with bit
of the feature register, the terminal sets
its output to the user activation value in place of the manufacturer switch-on value on the occurrence of a
system reset or a watchdog timer overflow (terminal has not received any process data for 100 ms).