Access from the user program
KL3403
55
Version: 3.1.0
Note the permissible range of the measured value output
The KL3403 should only take the transformer ratio into account if the calculated resulting current
does not exceed the value 65535!
If the calculated result does exceed 65535, the transformer ratio should be taken into account in the
PLC.
R38: Time constant for automatic deletion of the minimum and maximum values
If bit
is enabled, the minimum and maximum current, voltage and power values of the respective
phase are cleared after the set time.
• Default value: 2000 ms (R38 = 200)
• Resolution: 10 ms
• Range of values: 10 ms to 655350 ms
R39: Measuring cycle time
With this register, the measuring cycle time of the A/D converter is set:
• Default value: 50 ms
• Resolution: 1 ms
• Range of values: 1 ms to 65535 ms
The correct setting of the measuring interval depends on the mains frequency, among other factors (see
chapter
5.6
Examples of Register Communication
The numbering of the bytes in the examples corresponds to the display without word alignment.
5.6.1
Example 1: reading the firmware version from Register 9
Output Data
Byte 0: Control byte
Byte 1: DataOUT1, high byte
Byte 2: DataOUT1, low byte
0x89 (1000 1001
bin
)
0xXX
0xXX
Explanation:
• Bit 0.7 set means: Register communication switched on.
• Bit 0.6 not set means: reading the register.
• Bits 0.5 to 0.0 specify the register number 9 with 00 1001
bin
.
• The output data word (byte 1 and byte 2) has no meaning during read access. To change a register,
write the required value into the output word.
Input Data (answer of the bus terminal)
Byte 0: Status byte
Byte 1: DataIN1, high byte
Byte 2: DataIN1, low byte
0x89
0x33
0x41
Explanation:
• The terminal returns the value of the control byte as a receipt in the status byte.
• The terminal returns the firmware version 0x3341 in the input data word (byte 1 and byte 2). This is to
be interpreted as an ASCII code:
◦ ASCII code 0x33 represents the digit 3