Access from the user program
KL3403
47
Version: 3.1.0
5.2
Control and status bytes
Control and status byte of the first channel (L1)
Process data mode
Control byte 1 in process data mode
Control byte 1 (CB1) is located in the
, and is transmitted from the controller to the
KL3403. Note the assignment of the control bytes to the process input data words.
Bit
CB1.7
CB1.6
CB1.5
CB1.4
CB1.3
CB1.2
CB1.1
CB1.0
Name
RegAccess
R/W
ChannelIdx
ProcDatIdx
Key
Bit
Name
Description
CB1.7
RegAccess
0
bin
Register communication off (process data mode)
CB1.6
R/W
0
bin
Read access
(1
bin
)
Since the process data registers of the KL3403 can only be read, write access is not
sensible.
CB1.5 to
CB1.4
ChannelIdx
5
Enter the channel index of the channel, from which you want to read a measured value with input data
word 1 (
).
00
bin
Channel 1
01
bin
Channel 2
10
bin
Channel 3
11
bin
reserved
CB1.3 to
CB1.0
ProcDatIdx
Enter the process data index of the measured value, which you want to read with input data word 1
(
). The following process data indices are supported:
Index
Symbol
Measured value
Resolution
0000
bin
0x0
I
rms
value)
0.001 A (KL3403-0000, KL3403-0026)
0.005 A (KL3403-0010)
20 µA (KL3403-0020)
5 µA (KL3403-0022)
250 µA (KL3403-0025)
333 µV (KL3403-0333)
0001
bin
0x1
U
rms
value)
0.1 V
0010
bin
0x2
P
0.1 W (KL3403-0000, KL3403-0026)
0.5 W (KL3403-0010)
2 mW (KL3403-0020)
flexible, max. 16,000 digit (KL3403-0022)
6
25 mW (KL3403-0025)
flexible, max. 16,000 digit (KL3403-0333)
6
0011
bin
0x3
cos φ
4
0.01
0100
bin
0x4
W
Energy consumption
1
default
3
: 0.01 kWh (KL3403-0000,
KL3403-0026)
default
3
: 0.05 kWh (KL3403-0010)
default
3
: 0.2 Wh (KL3403-0020)
flexible (KL3403-0022)
6
default
3
: 2.5 Wh (KL3403-0025)
flexible (KL3403-0333)
6
0101
bin
0x5
I
max
Peak current value
2
see index 0
dec
0110
bin
0x6
U
max
Peak voltage value
2
see index 1
dec
0111
bin
0x7
P
max
Peak active power
value
2
see index 2
dec
1000
bin
0x8
f
0.1 Hz (measuring interval: 5 s)
1001
bin
0x9
I
min
Minimum current
value
2
see index 0
dec
1010
bin
0xA
U
min
Minimum voltage
value
2
see index 1
dec
1011
bin
0xB
P
min
Minimum active
power value
2
see index 2
dec
further
reserved
Содержание KL3403 Series
Страница 1: ...Documentation KL3403 3 Phase Power Measurement Terminals 3 1 0 2019 09 20 Version Date...
Страница 2: ......
Страница 4: ...Table of contents KL3403 4 Version 3 1 0...