Mounting and wiring
KL3361 and KL3362
25
Version: 2.2.0
Supply of the measuring bridge from an external voltage source
Note the following if the measuring bridge is supplied from an external voltage source:
The external supply voltage
• must also be applied to the UV+ and UV- connections for reference;
• must be within the range +5 V to +10 V;
• must not vary by more than ±5% during operation.
Fluctuations of the external supply voltage increase the measurement error!
After changing the external supply voltage, the oscilloscope terminal has to be restarted for re-
balancing!
The internal voltage source switches off automatically, as soon as an external voltage of more than 5 V is
applied to the UV+ and UV- terminals of the oscilloscope terminal.